TROUBLESHOOTING GUIDE

SYMPTOM OR DIFFICULTY

POSSIBLE CAUSE

REMEDY

A. Lithium bromide

solidifies at start-up.

1. Condenser water too cold.

1. a. Reset cooling tower bypass

valve to design conditions.

b. Check cooling tower fan con­

trol setting.

2. Air in machine.

2. Purge the machine. Use Carrier

Standard Service Techniques,

publication SM-16.

3. Improper purging.

3. a. Check to see that all valves

are in correct position.

b. Check machine leak rate with

purge.

B. Lithium bromide

solidifies during
operation.

1. Condensing water too cold.

1. a. Reset cooling tower bypass

valve to design conditions.

b. Check cooling tower fan con­

trol setting.

2. Steam pressure above design.

2. Reset to design conditions.

3. Vapor condensate temperature

too low. (Temperature should
never be below 114 F at full
load.)

3. Reduce condensing water flow.

4. Machine requires octyl alcohol.

4. Add octyl alcohol. Use Carrier

Standard Service Techniques,
publication SM-16.

5. Improper purging.

5. See Remedy in A-3 above.

6. Air leakage.

6. Leak test machine.

C. Low capacity

1. Air in machine.

1. Find and repair leak. Purge the

machine.

2. Condenser tubes dirty. Noted by

continually rising vapor con­
densate temperature (above 114
F) at full load.

2. Clean the tubes and take cor­

rective action in water treat­
ment methods. Use the Carrier
Standard Service Techniques,
publication SM-16.

3. Improper purging.

3. See Remedy in A-3.

4. Machine needs octyl alcohol.

4. Add octyl alcohol. Refer to

Carrier Standard Service Tech­
niques, publication SM-16.

5. Improper setting of capacity

control valve.

5. Reset capacity control valve to

design temperature by turning

control point adjuster down.

6. Insufficient condensing water

flow, or temperature too high.

6, a. Reset cooling tower bypass

valve to design temperature,

b. Check operation of tower fan.

c. Check the condenser water

strainer.

7. Solution temperature generator

below design at full load. Note
correct temperature at full load.

7. a. Raise steam press, to design.

b. Unplug the steam strainer

or trap.