Do not use drain line smaller than size listed in

Table 5. If required, cut hole in panel for drain line.

Piteh drain downward toward an open drain sump.
Provide a trap at least 3 in. high with plugged tee for

cleaning. Fill trap with water to make an air seal.

Observe all sanitary codes.

Step 14 — Make Electrical Connections

GENERAL — Provide an adequate fused dis­

connect switch per NEC within sight from the unit.

Provision for locking switch open (OFF) is ad­

visable to prevent power from being turned on when
unit is being serviced.

On all units, power may be supplied thru a branch

circuit. Branch circuit protection is provided in these
units by manual reset circuit breakers. Branch
circuit must be in accordance with NEC or local
code, whichever takes precedence. Power supplied
to auxiliary equipment, such as fan motors for air­

cooled condenser or for cooling tower, must be

run separately.

^POWER WIRING — Conduit opening for 016-034

units is on back of unit near control box. Conduit
opening for 044-064 units is on top of unit near
control box. On all sizes, field power connections
are made at a terminal block within the control box
(see Fig. 19). Refer to Table 6 for maximum wire
size at terminal block.

50BJ,BKOI6-034

FIELD
POWER
SUPPLY

---------------------------------------0L3 0-

------ O L2 O-

----------- OLI O-

-01

EQUIP. GND.

BLU

YEL

BLK

50BJ.BK 044-064

TBI

FIELD
POWER
SUPPLY

L3

L2

LI

llU

ÜU

rm

ÜU

IfTl—1

---------------- —7

iV 1 1

EQUIP. GND,

-------------------FIELD WIRING

-------------------- FACTORY WIRING

Fig. 19 — Field Power Wiring Connections

Supply voltage must be in accordance with name­

plate voltage. On 3-phase units, voltage between
phases must be balanced within 2% and current
within 10% with compressor running. If supply
voltage is not in accordance with nameplate voltage,
a phase unbalance may occur. Voltage at com­
pressor must be within the minimum and maximum

shown in Table 7.

Contact local power company for line voltage

corrections. Never operate a motor where a phase

unbalance in supply voltage is greater than

2%.

Use

the following formula to determine the % voltage
unbalance:

max voltage deviation

% Voltage _ jQQ from average voltage

Unbalance ~

average voltage

Example; Supply voltage is 240-3-60.

A B r, AB = 243 volts

BC = 236 volts
AC = 238 volts

Average Voltage =

Average Voltage

243 + 236 + 238

717

= 239 volts

Determine

maximum

deviation

from

average

voltage:

(AB) 243 — 239 = 4 volts
(BC) 239 — 236 = 3 volts
(AC) 239 -- 238 = 1 volt

Maximum deviation is then 4 volts. To determine

the % voltage unbalance:

4

1

Voltage Unbalance = 100 x

239

= 1.7%

This amount of phase unbalance is satisfactory

since it is below the maximum allowable of 2%.

IMPORTANT: ff supply voRage phase «a-

balaace

h

more than 2%, contaci your local

electric tiiility company immedjaieiy.

^

Compressor operation on improper line voltage

or excessive phase unbalance may be considered

abuse and anv resulting damage may not be covered

by Carrier warranty.

All wiring must be in accordance with local or

NEC regulations.

EIELD CONTROL WIRING — On extended volt­

age (208-230-v) units, control transformer is factory
wired for 208-v usage. If unit is to be used on 230-v
system, reconnect primary wiring on transformer as
shown on unit wiring diagram.

When accessory timer control panel is used,

connect

panel

to

factory-supplied

control

panel

as indicated on unit label diagram.

^WINTER

START-UP

PACKAGE

On

50BK

044-064 units, an accessory winter start-up package

is available for providing a 3-minute time delay by
shorting out the low-pressure switch on each com­
pressor. This enables each compressor to start even

during low ambient conditions.