Table 7 — unit electrical data – Carrier 50BK User Manual

Page 14

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 6 — Maximum Wire Size for

Power Terminal Block*

VOLTS/PHASE

UNIT 50BJ.BK

016

024

028,034

044t

054,064t

208-230/3

2/0

2/0

350

350

500

460/3

2/0

2/0

2/0

350

350

575/3

2/0

2/0

2/0

350

350

*Select wire size per NEC and connect supply wires to factory-

supplied pigtail wire connectors

tMaximum wire size for 50BJ,BK044 units with alternate drive

package is 500 MCM

IMaximum wire size for 50BJ.BK054 units with standard drive

package is 350 MCM

Table 7 — Unit Electrical Data

UNIT

VOLTS/PH/HZ

VOLTAGE

RANGE

COMP #1

COMP #2

INDOOR

FAN MOTOR

POWER

SUPPLY

Min

Max

RLA

LRA

RLA

LRA

Hp

FLA

MCA*

MOCPt

208-230/3/60

187

254

50 0

191

3

9 2

71 7

110

50BJ016

460/3/60

414

508

22 1

86

_

3

4 6

32 2

50

575/3/60

518

632

17 9

69

3

3 7

26 2

40

208-230/3760 n

187

254

36 0

137

36 0

137

5

13 2

94 2

125

50BJ024

460/3/60

414

508

160

62

160

62

5

6 6

42 6

50

575/3/60

518

632

129

50

12 9

50

5

5 6

35 1

45

208-230/3/60

187

254

^ 49 3

191

35 7

137

T/2

22 0

М2У0

150

50BJ028

460/3/60

414

508

22 2

86

16 0

62

I'h

11 0

54 8

70

575/3/60

518

632

180

69

13 0

50

I'h

8 7

44 2

60

208-230/3/60

187

254

49 3

191

49 3

191

IVi

22 0

132 9

175

50BJ034

460/3/60

414

508

22 2

86

22 2

86

I'A

11 0

61 0

80

575/3/60

518

632

180

69

18 0

69

I'h

8 7

49 2

60

208/230/3/60

187

254

57 9

283

57 9

283

15

46 2

178 5

225

50BJ044

460/3/60

414

508

26 5

142

26 5

142

15

21 0

82 7

100

575/3/60

518

632

22 2

98

22 2

98

15

15 4

64 7

80

208/230/3/60

187

254

80 8

446

60 0

283

20

59 4

222 4

300

50BJ054

460/3/60

414

508

35 8

223

26 5

142

20

27 0

100 3

125

575/3/60

518

632

30 0

164

22 2

98

20

20 0

81 5

110

208/230/3/60

187

254

91 5

446

91 5

446

25

74 8

282 7

350

50BJ064

460/3/60

414

508

42 6

253

42 6

253

25

34 0

131 9

150

575/3/60

518

632

32 2

164

32 2

164

25

25 6

100 1

125

208-230/3/60

187

254

64 0

266

3

9 2

89 2

150

50BK016

460/3/60

414

508

29 0

120

_

3

4 6

40 9

60

575/3/60

518

632

23 0

96

3

3 7

32 5

50

208-230/3/60

187

254

45 0

170

45 0

170

5

13 2

114 5

150

50BK024

460/3/60

414

508

20 0

77

20 0

77

5

6 6

51 6

70

575/3/60

518

632

160

62

16 0

62

5

5 6

41 6

50

208-230/3/60

187

254

64 0

266

45 0

170

Th

22 0

147 4

200

50BK028

460/3/60

414

508

29 0

120

20 0

77

T/2

11 0

67 3

70

575/3/60

518

632

23 0

96

17 0

62

T/2

8 7

54 7

70

208-230/3/60

187

254

64 0

266

64 0

266

T/2

22 0

166 0

200

50BK034

460-3-60

414

508

29 0

120

29 0

120

I'h

11 0

76 3

100

575/3/60

518

632

23 0

96

23 0

96

I'h

8 7

60 5

80

208/230/3/60

187

254

77 2

345

77 2

345

15

46 2

221 9

250

50BK044

460/3/60

414

508

35 8

173

35 8

173

15

21 0

103 6

125

575/3/60

518

632

30 0

VO

30 0

120

15

15.4

84.9

110

208/230/3/60

187

254

101 5

446

77 2

345

20

59 4

265 5

350

50BK054

460/3/60

414

508

48 6

223

37 9

173

20

27 0

127 7

175

575/3/60

518

632

38 6

164

30 0

120

20

20 0

100 3

125

208/230/3/60

187

254

120 0

506

120 0

506

25

74 8

346 8

450

50BK064

460/3/60

414

508

56 5

253

56 5

253

25

34 0

163 2

200

575/3/60

518

632

42 9

176

42 9

176

25

25 6

124 2

150

FLA

— Full Load Amps

Hp

— Nominal Horsepower

LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection Device (amps)
RLA — Rated Load Amps

*Minimum circuit amps (MCA) for wire sizing complies with NEC Section

430-24

fin compliance with NEC requirements for multi motor and combination load

equipment (Ref NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse only

NOTES:

1 Compressor circuit breakers are current sensitive and temperature

compensated to ensure compressor cutoff if current draw becomes
excessive Breakers must be manually reset

Discharge gas thermal protection or internal protection with automatic
reset de-energizes the control circuit if extreme compressor motor

temperature should occur from excessive gas temperature or motor

overloading
Low- and high-pressure switches automatically shut off compressor(s)
if refrigerant pressure exceeds switch settings This action protects
against loss of charge
Indoor fan motor circuit breaker protects against motor overload Breaker
requires manual reset

The 50BJ,BK units are ETL listed at 208/230 and 460 v and C S A certi­
fied at 575

V

Phase imbalance shall not exceed 2%

Wire sizing amps are a sum of 125% of the FLA for the largest motor plus

100% of FLA for all other motors in the unit

Maximum instantaneous current flow during starting is the sum of the
LRA for last compressor to start plus the FLA for all other compressors in
the unit