Carrier 07E User Manual

Compressors and condensing units, Carrier, Hermetic, water-cooled

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Carrier

installation, Start-Up ncsc H7F

and Service Instructions WOC,u/C

Compressors and Condensing Units

Hermetic, Water-Cooled

PRELIMINARY SURVEY

Inspect shipment for damage. File claim with

the shipping company if shipment is damaged or
incomplete.

Locate unit on floor in a well ventilated area.

Install unit where it will be warmer than condi­
tioned area. Position it to allow sufficient space for
refrigerant and water connections and to service

compressor. Allow space at one end of condenser

for tube cleaning or replacement. Place unit so
suction and discharge valves can be easily reached
and so oil level can be checked.

Local water conditions can cause excessive

fouling or pitting of condenser tubes. If such
conditions are anticipated, a water treatment
analysis is recommended. Refer to Carrier System
Design Manual, Part 5, for general water condi­
tioning information.

Make provision in piping layout to drain and vent

condenser if system is to be shut down in winter.

Level unit and bolt it firmly to foundation.

Remove 4 self-locking bolts from compressor­
mounting springs, and reassemble them with

flanged washers and neoprene snubbers as shown in
Fig. 1. Flanged washers and neoprene snubbers are
shipped in a cloth bag tied to compressor. Tighten
all 4 bolts. Then, loosen each until the flanged
washer can be moved sidewise. Check compressor
to see that it floats freely on its mounting springs.

SMUBBER FLATBED
WASHER

MEOPRENE
SNUBBER

^COMPRESSOR FOOT

, tSOtATtON SPRiNO

Fig. 1 — Compressor Mounting

PIPING CONNECTIONS

Attach water supply and return line to connec­

tions indicated on condensing unit (Fig. 3). Water
leaving condenser should not be connected directly
into sewer lines; check local codes.

Attach refrigerant liquid and suction lines to

condensing unit (Fig. 3); suction and discharge
lines to compressor unit (Fig. 2). Discharge line
muffler supplied with 06EV,W compressor units is
installed in discharge line as close to shutoff valve
as possible. When soldering or brazing piping to

valves, disassemble the valve or wrap it in wet cloth

to prevent damage by heat. Allow flexibility in
suction line so compressor suction valve may be
moved aside for access to suction strainer.

Install a solenoid valve (field supplied) in liquid

hne directly before expansion valve. Solenoid valve
is necessary for single pumpout control used on
06E,07E units (refer to Start-Up and Service
Instructions). A filter-drier of adequate size should
be installed in liquid line between condenser and
solenoid valve.

Pressure relief valve located on side of con­

denser will open to relieve excessive pressure,
allowing refrigerant to escape. Most local codes
require piping from valve to outdoors.

Refer to Carrier System Design Manual for

standard piping techniques.

Table 1 — Physical Data

COMPRESSOR UNIT 06E

d P E R A fjNjG W E (G H T (fb)

CONDENSING

UNIT

07E

OPERATING WEIGHT (lb)

refrige

Y

nt

COMPRESSOR 06E

Oil Charge (pt) (PP33-2)
Normal Oil Pressure*

Oil Safety Switch Cut-In

Cutout

High-Pressure Switch

Cutout Range

V022

W027 1 W033

W044

6Ô0

650

' 670

BO 22

B027^

.

1

,

B033

D044

1275

1340 1 1350

1560

R-22, R-502^

D250

0265 I F 275

E299

D150

N265 ; N175

N599

14

16 i

Î9

12-18 psig

8-10 psig

4- 5 psig

Differential (cutout, cut-in) f
Factory Settings f Cutout '

Cut-in i

230 to 400 psiq (adj)

23G to

340 p'ji ;g (ccj)

, 80 ±

10 psi

(fi xed)

370 ±

7 Dsig

28C i
290 +

7 psig

200

±

7 psic

Low-Pressure Switch

Cutout Range

Differential (cutout, cut-in)
Factory Settings! Cutout

Cut-in

Low Side Max Pressure

CONDENSER DATA

Max Refrigerant (R-22)

Storage Capacity (lb)

t

Min Refrigerant (R-22)

Operating Charge (Ib)

Max Operating Pressure

Refrigerant Side

Water Side

20 in Hg vac to 60 psig (adj)
20 in Hg vac to 70 psig (adj)

31 psi (adj 13 to 50)

36 + 4 psig
67 + 4 psig

245 psig

135

' 33

335 psig
250 psig

193

37

J 07E Conidensing Unit data

* Pressures noted are above operating suction pressure; i.e , pressure

differential between suction pressure and discharge pressure of oil
pump.

Î Pressure switch settings shown are for R-22. When using other

refrigerants, reset high- and low-pressure switch settings to
pressures corresponding to satuialion temperatures indicated by

the above pressures.

\

Condenser 80% filled with liquid refrigerant at 104 F,

© Carrier Corporation 1972

Form 06E,07E-4SI

Advertising