Table 2 — electrical data, Electrical requirements, Accessories – Carrier 07E User Manual

Page 3

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 2 — Electrical Data

volts

/

pha

U

208/3

230/3

NDSV

208

220-240

COND

Wire

Max

Fusetron

Wire

Max

Fusetron

UNIT

KW

LRA

FLA

OLTA

Size*

Ft

Si ze

LRA

FLA

OLTA

Size*

Ft

Size

07 E

(AWG No.)

Wire

(Amps)

(AWG No.)

Wire

(Amps)

B022

22 6

310

71

99

2

73

100

280

65

90 8

2

88

100

B027

31.4

457

86

121

0

62

125

410

82

116 0

0

78

125

B033

34 0

387

105

146

00

84

150

350

96

134 0

0

87

150

DO 44

50.4

586

126

176

00

71

200

530

126

176.0

00

80

200

COMPR

06 E

V022

24 8

387

78

109

1

79

110

350

71

99

2

80

100

W027

33.6

457

93

129

0

79

150

410

86

120

1

78

125

W033

37 6

464

115

160

00

77

175

420

105

146

00

94

150

W044

55.1

664

137

192

00

65

200

600

137

192

00

72

200

VOLTS/PHASE

460/3

575/3

NDSV

440-480

550-600

COND

Wire

Max

Fusetron

Wire

Max

Fusetron

UNIT

KW

LRA

FLA

OLTA

Size*

Ft

Si ze

LRA

FLA

OLTA

Size*

Ft

Size

07 E

(AWG No.)

Wire

(Amps)

(AWG No.)

Wire

(Amps)

B022

22 6

140

32

44 5

8

102

45

1 12

27

36 7

8

151

40

B027

31 4

205

41

57 8

6

122

60

164

34

48 3

6

183

SO

B033

34 0

175

48

66 0

4

158

70

140

38

53 3

6

165

60

D044

50.4

265

61

85.4

2

132

90

212

53

73.4

4

185

80

COMPR

06 E

V022

24 8

175

35

48 3

6

143

50

140

28

38 6

8

147

40

WO 27

33 6

205

43

60 2

6

116

70

164

34

48 3

6

183

50

W033

37 6

210

52

71 6

4

145

75

168

42

58 0

6

150

60

W044

55 1

300

69

96.0

2

121

100

240

56

78 0

4

171

80

FLA

— Full Load Amps

LRA — Locked Rotor Amps

IMDSV — Nominal Distribution System Voltage (Application Range)

-- Motorsand controlswill operate satisfactorily 10% above

and 10% below the NDSV (Application Range)

OLTA — Overload Trip Amps

*Wire size to terminal box (line side)

NOTES:

1. 208-, 230-volt 06E compressor units and 07E condensing units

have part-winding start 460-, 575-volt units have across-the-line

start, except 06EW044 and 07ED044 which have part-winding
start Control circuit voltage is 11 5 volts for all units.

5.

Factory wiring is in compliance with National Electrical Code.
Field wiring must comply with appiicable local codes Maximum

wire size to control center line terminal block is 250 MCM.
Where compressor FLA is under 100 amps, wire sizes are based
on type TW wire. Where compressor FLA is over 100 amps, wire
sizes are based on type TFIW wire

Maximum wire lengths tabulated will result in a 1% voltage drop

to compressor A 3% voltage drop is maximum allowed.Therefore,
the run length can be increased to three times the value given.
Above 06E compressor unit electrical data does not apply for
06E compressors used as an integral part of other Carrier equip­

ment See proper Start-Up and Service book for electrical
information

ELECTRICAL REQUIREMENTS

Field wiring must comply with local and

national codes.

Install a branch circuit fused disconnect of

adequate size to handle starting current.

Line power is brought into control center thru

indicated opening. Connect line power supply to
terminal block 1; connect power leads to terminals

LI, L2 and L3. Connect control circuit power

supply (115 volt) to terminals 1 and 2 on terminal
block 2. Refer to Fig. 4 and 5.

Wiring connections for field-supplied equip­

ment are shown on diagram attached to unit (or in
wiring diagram booklet).

Discharge line limit thermostat supplied with

06EV,W compressor units is installed on discharge
hne as close to compressor as possible.

plate on discharge line and

to plate with screws

1. Place mounting

solder in place.

2. Fasten the thermostat

supplied.

3. Cover switch with insulation and secure insula­

tion at each end with straps.

4. Connect thermostat leads to control circuit

terminals 4 and 5.

ACCESSORIES

PACKAGE NUMBER

DESCRIPTION

07EA900021

Control Circuit Transformer

07EA900001

Gage Panel

Advertising