for cooling and outdoor ambient temperature is

above outdoor air thermostat setting. The econo­
mizer damper moves to VENT position.

Evaporator fan starts and economizer damper

opens fully upon a first-stage call for cooling when
outdoor ambient temperature is below the outdoor
air thermostat setting. Compressor remains off.

Compressor is energized and mechanical cooling

integrates with economizer cooling upon a second-
stage call for cooling.

Mechanical cooling is locked out when ambient

temperature is below 50 F.

Economizer damper modulates when mixed air

temperature is below mixed air thermostat (non-

adjustable) setting.

An economizer control thermostat (ECT) is

located on the evaporator coil. This thermostat
guards against abnormally low suction tempera­
tures while operating mechanical cooling in con­

junction with economizer. Low suction tempera­

tures can lead to frosting on the evaporator coil.

If frost buildup is detected, thermostat turns off

economizer, thus closing the outdoor air damper.

This raises air temperature entering the evaporator

coil and melts frost. Once frost is melted, the

economizer is re-energized.

During unoccupied periods, if a field-supplied

night switch is used and is opened, the outdoor air

damper closes.

HEATING MODE — Outdoor air damper stays at
VENT position while evaporator air fan runs. If

field-supplied night switch is used, the outdoor air
damper closes when switch is open.

SERVICE

Cleaning — Inspect unit interior at the beginning of
each heating and cooling season or as operating
conditions require. Remove unit side panels for
access to unit interior.

EVAPORATOR COIL

1. Turn unit power off.

2.

Disconnect evaporator motor and electric

heater(s) from main control box.

3. Remove top panel screws shown in Fig. 23.

4. Remove screws from base of evaporator fan

housing and electric heater plate.

5. Pry up top panel to clear top of evaporator fan

housing. See Fig. 23.

6. Remove evaporator fan housing, heaters and

heater plate from unit.

7. Use commercial coil cleaner (Oakite 164), or

dishwasher detergent in a pressurized spray

cannister. Wash both sides of coil and flush with

clear water. For best results, backflush towards

return air section to remove foreign material.

Flush condensate pan after completion.

8. Replace evaporator fan housing, electric heater(s)

and all wires.

Fig. 23 — Removing Top Panel

Fig. 24 — Cleaning Condenser Coil

CONDENSER COIL —^ Inspect coil monthly.

Clean condenser coil annually, or as required by

location or outdoor air conditions.

Fins are not continuous thru coil sections. Dirt

and debris may pass thru first section, become
trapped between the 2 rows of fins, and restrict con­
denser airflow. Shine flashlight thru coil to deter­

mine if dirt or debris has collected between coil
sections.