Outdoor Air Intake (50CD008) — The 50CD
can be equipped with an optional outdoor air

damper or an economizer that mixes outdoor air
with return air.

Field-Fabricated Ductwork

50CD — See Fig. 3. Secure all ducts to roof curb and
building structure before unit is placed on curb.

Do not connect ductwork to unit.

Cabinet return air static shall not exceed 0.35 in.

with economzier or 0.40 in. without economizer.

50CH — See Fig. 4. Secure all ductwork to flanges

on unit supply air and return air openings and
building structure.

50CD/CH — Insulate and weatherproof all ex­

ternal ductwork, joints and roof/ wall openings with
flashing and mastic in accordance with applicable
codes. Insulate ducts passing thru an unconditioned

space and cover with a vapor barrier.

A minimum clearance is not required for any air

duct installation.

Optional Manual Outdoor Air Damper (50CD
008) — Optional outdoor air damper is shipped
with hood broken down in unit filter section.
See Fig. 5.

ASSEMBLY

1. Remove protective polyethylene cover from unit.

See Fig. 5.

2. Remove upper filter access panel (save screws).

See Fig. 5.

3. Remove hood parts from unit evaporator fan

and filter area. Assemble hood top and side

plates as shown in Fig. 6. Do not attach hood to

unit at this time.

4. Adjust outdoor air damper blade to desired

setting for outside air intake by releasing linkage

rod setscrew and adjusting linkage rod. See

Fig. 7. Secure damper blade in desired position

with setscrew.

5. Remove screws holding manual outdoor air

damper to unit. See Fig. 8.

Install outdoor air hood assembly, using screws

from step 5. These screws secure the manual

outdoor air damper assembly and the outdoor

air hood to unit. See Fig. 9.

Slide outdoor air inlet screens into screen tracks
on hood side plates. While holding screens in
place, fasten screen retainer to hood using screw
provided. Make sure bottom edge of screens rest

inside base rail as shown in Fig. 9.

Replace upper access panel with screws saved

from step 2.

9. To check percentage of ventilation air entering

unit, proceed as follows:

a. If unit power is on, turn it off.
b. Jumper red and black wires in 24-v barrier

in main control box. See Fig. 10.

c. Turn on unit power to energize evaporator

(indoor) fan.

6

.

7.

8

.

Fig. 5 — Access Panel Location

t

Fig. 6 — Outdoor Air Hood Details

d. Check percentage of ventilation air entering

unit. If percentage varies from that specified,

remove upper filter access panel and adjust
damper blade as described in step 4. Proce­
dure may have to be repeated until proper

percentage of ventilation air is attained.

e. Turn off power. Remove jumper between

red and black wires.

f. Replace upper filter access panel.

50CH008 Unit Assembly — Remove packaging
and tape from evaporator fen drive system.

Evaporator Air Fan — Evaporator fan uses a belt-

drive motor which provides high static at nominal
airflow. The standard motor provides approxi­
mately 0.95 in. static at nominal cfm and the alter­

nate motor provides 1.0 in. static at nominal cfm.