Calibrating Electronic Controls

- Honeywell Only (Fig. 4)

Table

4 -

Chilled Water Module

SEQUENCE

PROCEDURE (Compressor Operating)

1. Set Differential

Adjustment

A. Place capacity control switch (8) in MANUAL position.
B. Set throttling range screw (19) on counterclockwise stop.
C. Operate machine manually until leaving chilled water temperature is

within the range of the chilled water thermostat (35 F to 55 F).

D. Adjust differential screw (15) for a 3/4 F movement of the chilled water

thermostat (4) between the operation of relay CRO (25) and CRC (24).

2. Calibrate Chilled

Water Temperature
Setting

A. Open vanes manually until chilled water temperature reaches design

temperature. Place chilled water thermostat in center of dial. (Lowest
division on left corresponds to 35 F. Each division represents I F . )

B. Adjust calibration screw (17) until relay CRC (24) is closed and relay

CRO (25) is open.

3. Adjust Capacity

Balance

A. Connect an a-c voltmeter across test jack (21) and terminal J28. Use

50- or 60-volt scale.

B. Turn chilled water thermostat (4) clockwise or counterclockwise to

obtain lowest voltage reading on voltmeter.

C. Turn capacity balance screw (16) clockwise or counterclockwise until

voltage decreases further.

D. Repeat above steps to decrease voltage to approximately one volt.

4. Observe Automatic

Operation

A. Place capacity control (8) on THERMO position and thermostat (4) at

design chilled water temperature.

B. Turn throttle range screw (19) clockwise 1/3 of its total travel if chilled

water temperature "hunts.”

C. Recalibrate as in sequences 1 thru 4.

Calibrating Electronic Controls

- Barber-Colman Only (Fig. 5)

Table 5 - Chilled Water Module

SEQUENCE

PROCEDURE (Compressor Operating)

1. Adjust Capacity

Balance

A. Rotate throttling range screw (17) to counterclockwise position.
B. Operate vanes manually until chilled water temperature drops to design

temperature.

C. Place capacity control switch (15) on HOLD.
D. Set chilled water thermostat (3) to dial center. (Lowest division on left

corresponds to 35 P. Each division represents I E . )

E. Connect COMMON plug of an a-c voltmeter to terminal X on amplifier

and other plug to terminal T. Use 12-volt scale.

F. Adjust temperature bridge calibration screw (18) until voltage becomes

minimum.

G. Adjust capacity balance screw (16) until voltage decreases further. Re­

peat steps above to decrease voltage to one volt or lower.

H. Remove voltmeter.

2. Differential Setting

NOTE: A differential resistor is factor^'installed between terminals X

and Y (10) OR the cMlled water amplifier to give approximately 1 F dif- ;

ferential between the operation of microrelays CRC and CRO (19).

3. Observe Automatic

Operation

A. Place capacity control switch (15) on AUTO position.
B. Rotate throttling range screw (17) clockwise 1/3 of total travel if chilled

water temperature "hunts."

NOTE: If timottling range is added, recalibrate as in sequences 1 thru 3.