Table 4A — Physical Data, 38AN Cooling Only Condensing Units*

UNIT 3SAN

009

012

NOMINAL CAPACITY (Tons)

%

1

OPERATING WEIGHT (lb)

55

62

REFRIGERANT TYPE

R-22

Control (Cooling)

Capillary Tube

Factory Charge (lb)

1.5

1.8

COMPRESSOR TYPE

Carrier Hernietic Rotary

Model

EAA090111A

E8B120111A

Oil (Recharge) (oz)

10.1

10.1

Crankcase Heater

None

Accumulator

Yes

OUTDOOR FAN

Propeller, Direct Drive

Rpm

850

850

Diameter (in.)...No. of Blades

12y4...4

12У4...4

Motor Watts

87

87

Nominal Air Cfm

750

750

OUTDOOR COIL

Copper Tube, Aluminum Fin

Face Area (sq ft)...No. of Rows

3.5...1

3.5...2

FIns/in.

18

17

CONTROLS

Fusible Plug (F)

210

210

Control Voltage

115

230

REFRIGERANT LINES

Connection Type

Male Flare

Liquid Line OD (in.)

У4

'/4

Vapor Line OD (in.t

Maximum Length (ft)

35

35

Maximum Lift Fan Coil (Above Outdoor) (ft)

16

16

Maximum Lift Fan Coil (Below Outdoor) (ft)

30

30

‘These units may only be used with 40QNB009,012 fan coil units.

Table 4B — Physical Data, 40QNB Cooling Only High Wall Units

UNIT 40QNB

009*

012*

NOMINAL CAPACITY (Tons)

n

1

NOMINAL SIZE (Btuh)

9000

12,000

OPERATING WEIGHT (lb)

18.7

24.2

MOISTURE REMOVAL RATE (Pints/Hr)

2.4

3.4

FINISH

White

REFRIGERANT

R-22

Control (Cooling)

Capillary Tube in Outdoor Unit

Factory or System Charge (ib)t

1.5

1.8

INDOOR FAN

Direct Drive Centrifugal

Rpm...Cfm High

1200...240

1040...260

Rpm...Cfm Medium

1100...210

940...240

Rpm...Cfm Low

1000...180

850...210

Motor Watts

34

35

Biowers — No. ...Size (in.)

1...3.54

X

27.75

1...3.94X 27.75

INDOOR COIL

Copper Tube, Aluminum Fin

Face Area (sq ft)

1.45

1.6

No. of Rows

2

2

Finsfin.

18

17

Circuits

2

3

FILTERS

Cieanable

(Quantity) Size (in.)

(2) 9x 12

(2) 914 X 13W

AIRSWEEP

Horizontai

Manual

Vertical

Automatic

CONTROLS

integrated Microprocessor

Remote Controller

Wireless

Freeze Protection

Yes

Auto. Restart

Yes

Diagnostics

Yes

Timer Mode

24-Hour Startup/Shutdown Type

Test Mode

Yes

Dehumidification Mode

Yes

Fan Mode

Hig h/Medium/Low/Auto.

Control Voltage

115 V

230 V

REFRIGERANT LINES

Connection Type

Male Flare

Liquid Line OD (in.)

W

14

Vapor Line OD (In.)

14

'4

Maximum Len^h (ft)

35

35

Maximum Lift Fan Coil (Above Outdoorl (ft)
Maximum Lift Fan Coll (Below Outdoor) (ft)

16

16

30

30

CONDENSATE DRAIN CONNECTION (in.)

OD,

Vie

ID

•Units may only be matched with 38AN outdoor units.

tFull factory charge shipped in outdoor unit. Charge is determined based on 25 ft of line.