Start-up – Carrier 19EA User Manual

Page 5

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

on relay nameplate. Oil is shipped in small vials
usually attached to starter frame near relays.

Use only the dashpot oil shipped with starter.

Do not substitute. Overload relays are factory

set for 108 percent of motor full load amper­

age. Resetting is not normally required.

4. Check transfer timer for proper time setting.

On Star-Delta starters, timers have adjustable
ranges of 10 seconds to 3 minutes and are

factory

set

for

one

minute.

On

Auto-

Transformer starters, timers have adjustable

ranges of 0 to 60 seconds and are factory set

for 30 seconds.

5. With main disconnect switch open, manually

open and close main control relay (ICR) to be

sure it operates freely.

Oil Charge

is shipped in the oil reservoir. Check

sight glass ( 1 4 ) to be certain oil is visible. If oil

must be added, it must meet Carrier’s oil specifi­

cation. Charge oil thru the oil reservoir charging

valve ( 1 9 ) . Use a hand pump to charge the oil
against machine pressure.

Oil Heater

— Energize the oil heater to minimize

absorption of refrigerant by the oil. A light (16)
indicates when the heater is energized. Set the oil
heater

thermostat

to

maintain

a

minimum

temperature of 145 F at shutdown.

Refrigerant Charge

is shipped in the utility vessel.

If refrigerant must be added, charge it thru the

refrigerant charging valve (6).

WARNING; Never charge liquid refrigerant into

the unjshell if the pressure is helow 35 psig.
Bek>w 35 psig, R-12 will flash to a gas at a

temperature heiow the freezing pomt of water.

With cooler and condenser water fiownng,

charge the refrigerant as a gas tmiil the vessel

pressure is above 35 psig.

Refer to Trimming Refrigerant Charge for full

load adjustment.

Check Operation of Safety Controls

— As the

following checks are made, the panel lights

should appear as shown in the diagrams.

CONTROL LIGHTS

□ -OFF

■ l-ON

ON-STOP

START

OIL PUMP

POWER

SAFETY CIRCUIT

LOAD RECYCLE

PROGRAM TIMER

1

2

3A

3B

4

5

(SEE BELOW)

STEP

1. Disconnect main motor leads in starter.

2. Energize the control circuit.
3a. With water pumps off, press oil pump button

for several seconds to determine oil pressure
on differential gage. With pump running,

confirm that circuit between terminals

<Q> and ^ is closed by using an

ohmmeter.

b. Release the oil pump button. Circuit between

terminals ^ and

must open.

4.

Start the chilled water and condenser water

pumps. Confirm that circuit between terminals

and

is closed with pumps run­

ning, and opens when pumps stop and flow
switches open.

5.

Press ON-STOP button. If safety circuit light is

off, check resets on the condenser high-

pressure safety, cooler low-pressure safety,

bearing and motor high-temperature circuit
breakers and compressor motor overloads in
starter. Check 3-amp fuse in control center. If
safety circuit light is on but load recycle light

is off, check the automatic resetting chilled

water recycle switch. If both lights are on,
manually trip and then reset bearing and

motor high-temperature circuit breakers and

compressor motor overloads to be sure they
cut off the safety light. Tripping the chilled

water recycle switch will cut off the load
recycle light only.

CONTROL LIGHTS

□ -OFF

B-ON

N

■ ■

m

■ □ □

■ □ □

■ ■ ■

■ □ ■

■ □ ■

\ m

ON-STOP

START

OIL PUMP

POWER
SAFETY CIRCUIT

LOAD RECYCLE

PROGRAM TIMER

STEP

6A 6B 6C

8 {SEE BELOW)

6a. Press machine START button. (Motor leads

disconnected and water pumps running.)

b. Oil pump starts within 30 seconds.
c. Compressor motor start contacts will close 30

seconds later. Starter will transfer to its run
condition 30 to 60 seconds after starter is

energized.

7.

Open the oil pump main disconnect. Starter

must de-energize. Close disconnect.

8.

In approximately 15 minutes, the program

timer will complete the antirecycle portion of

its cycle and the machine may be started.

9.

Open circuit breaker and reconnect main

motor leads.

START-UP

Preliminary Checks

1. Power on to main circuit breaker, control

circuit, water pumps and tower fan.

2. Cooling tower water level.
3. Oil reservoir level and refrigerant level.

4. Oil reservoir temperature 145 F or warmer.
5. All isolation valves open. See (27), (28), (29)

and (30) of Fig. 1. If valves are closed, follow

isolation valve procedure on page 3.

6. Oil cooler plug cock, (36) Fig. 1, cracked open,

and any other valves in oil cooler line fully
open.