Iimstructiimg the customer operator – Carrier 19EA User Manual

Page 8

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

4. Turn the motor current calibration adjustment

fully clockwise. This will force the guide vanes
to close part way.

5. Turn the thermostat adjustment (item 4, Fig. 3)

to “Cooler” (fully counterclockwise).

6. Set the capacity control switch (item 2, Fig. 3)

to “Inc” position.

7.

Slowly turn the motor current calibration

adjustment

counterclockwise,

allowing

the

guide vanes to open until the motor current

reaches 5 percentage points above the electrical

demand setting.
NOTE: There is a time lag of several seconds

due to feedback capacitance in the motor
current circuit. When motor current calibration

setting is adjusted, this time lag should be
allowed for.

8. Check the foregoing motor current calibrations

with machine under “Auto” control as follows:
a. Close vanes manually (capacity control to

“Dec”).

b.

Turn capacity control to “Auto.” Vanes

should stop opening at electrical demand

setting.

9.

If control was calibrated at less than 100

percent load, turn electrical demand adjustment

setting to 100 percent. Control is now auto­
matically calibrated for 100 percent full load

motor current.
This is a two-step motor current limiting

circuit. At 100 percent full load motor current,

the vanes will stop opening any further. If the
motor current should increase to 105 percent

due to some change in load cpnditions, the

vanes will close until the motor current is
reduced to about 102 percent. If the motor

current is reduced to 98 percent or below, the

control will respond to leaving chilled water

temperature. The electrical demand adjustment
allows the operator to reduce the maximum

current drawn by the motor, minimizing the
electrical demand rate during the off season

operation.
NOTE: If control cannot be calibrated with

above procedure, check voltage signal from

signal resistor in starter. At 100 percent full
load current, voltage between terminals 23 and
24 inside control panel must be 0.5 ± 0.1 volts.

If not in this range, check sizing of resistor in
starter.

CHILLED WATER CALIBRATION PROCEDURE

1.

Turn throttle range calibration adjustment

(item 5, Fig. 3) fully clockwise.

2. Turn chilled water thermostat (item 4, Fig. 3)

until design chilled water temperature is main­
tained. Mark thermostat at this position. If

capacity control vanes hunt, turn throttle range
calibration

adjustment

counterclockwise

in

small increments until hunting ceases. Chilled

water thermostat may require resetting.

Trimming Refrigerant Charge

— After the machine

has been placed in operation, it may be necessary
to adjust the refrigerant charge to obtain optimum

machine performance.

When machine full load is available, add o,

remove refrigerant slowly until the difference
between leaving chilled water temperature and the

cooler temperature reaches design conditions or

becomes a minimum. Shut the machine down and

allow refrigerant level to equalize between vessels.

Mark the level indicator (items 23, 24 or 25, Fig.

1) and maintain that shutdown refrigerant level.

IIMSTRUCTIIMG THE CUSTOMER OPERATOR

Be sure the operator carefully reads the 19EA

Operating and Maintenance Instructions.

Point out the following components; explain

their function and the system in which they are
used.

Compressor

Guide vanes, vane motor and linkage

Refrigerant-cooled motor

Transmission

Unishell

Cooler, condenser

Relief valve, isolation valves

Utility Vessel

Float chambers, sight glasses
Relief valves, charging valve

Dehydrator

Importance of proper operation

Valves and system operation

Sight glasses, gage

Lubrication System

Oil pump, cooler, filter

Solenoid, plug-cock

Heater, thermostat, temperature gage

Oil level and temperature

Pumpout System

Compressor, condenser, oil separator
Valve designation and cycle

Control System

Manual switches, gages and lights

Operating controls, safety controls
AuxiUary and special controls

Auxiliaries

Starter(s), pumps, cooling tower

Describe Refrigeration Cycle
Review Maintenance

Scheduled, extended shutdown

Importance of Log Sheet Record
Importance of water treatment

Check Operator Knowledge

Start-stop procedure
Safety and Operating Controls

Carrier Service

Advise operator of availability, and method of

ordering parts.

Review Operating and Maintenance Instructions.

Manufacturer reserves the right to change any product specifications without notice.

C A R R I E R A I R C O N D I T I O N I N G C O M P A N Y • S Y R A C U S E ,

l E W Y O R K

Tatalnn Nn FS31-929

Advertising