Ik warning, I 5^k, Gas supply requirements – Sears 64182 User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

ià WARN ING

I

Exceeding the length of duct pipe or number

of elbows allowed in the “MAXIMUM LENGTH" charts

can

cause an accunnulation of lint in the exhaust systenn. Plugging

the systenn could create a fire hazard, as well as increase drying

tinnes.

ià WARNING

Do not screen the exhaust ends of the vent

system, nor use any screws, rivets or other fastening means

that extend into the duct and catch lint to assemble the
exhaust system.

Lint can beconne caught in the screen, on the

screws or rivets, clogging the duct work and creating a fire hazard

as well as increasing drying tinnes. Use an approved vent hood

to terminate the duct outdoors, and seal all joints with duct tape.

All male duct pipe fittings

MUST

be installed downstream with

the flow of air.

ik WARNING

Explosion hazard. Do not install the dryer

where gasoline or other flammables are kept or stored.

If

the dryer is installed in a garage, it must be a minimum of 18

inches (45.7 cm) above the floor. Failure to do so can result in

death, explosion, fire or burns.

Number

of

90°

Turns

MAXIMUM LENGTH

of 4"

(10.2 cm) Dia. Rigid Metai Duct

VENT HOOD TYPE

(Preferred)

(10.2 cm)

Louv

ired

i 5^k-

(6.35 cm)

0

60 ft.(18.28

m)

48 ft. (14.63

m)

1

52 ft.(15.84

mi

40 ft. (12.19 mi

2

44 ft.(13.41

m)

32 ft. (9.75 m)

3

32 ft.(9.75

m)

24 ft. (7.31 mi

4

28 ft. (8. S3

m)

16 ft. (4.87 mi

Number

of

90°

Turns

MAXIMUM LENGTH

of 4" (10.2 cm) Dia. Fiexibie Metai Duct

VENT HOOD TYPE

(Preferred)

(10.2 cm)

Louvt^red

i 5^k-

(6.35 cm)

0

30 ft. (9.14 m)

18 ft. (5.49

m)

1

22 ft. (6.71

mi

14 ft. (4.27 mi

2

14 ft. (4.27 mi

10 ft. (3.05 mi

3

NOT RECOMMENDED

than 0.75 inches of water column, the system is acceptable.

If the manometer reading is higher than 0.75 inches of water

column,

the

system

is

too

restrictive

and

the

installation

is

unacceptable.

Although

vertical

orientation

of

the

exhaust

system

is

acceptable,

certain

extenuating

circumstances

could

affect

the

performance

of the dryer:

Only the rigid metal duct work should be used.

Venting vertical through a roof may expose the exhaust system

to down drafts causing an increase in vent restriction.

Running the exhaust system through an uninsulated area may

cause condensation and faster accumulation of lint.

Compression or crimping of the exhaust system will cause an

increase in vent restriction.

The exhaust system should be inspected and cleaned a minimum

of

every 18 months

with normal usage. The more the dryer is

used, the more often you should check the exhaust system and

vent hood for proper operation.

EXHAUST DIRECTION

All dryers shipped from the factory are set up for rear exhausting.

However, on electric dryers, exhausting can be to the right or left

side of the cabinet or the bottom of the dryer. On gas dryers,

exhausting can be to the right side of the cabinet or the bottom of

the dryer. Directional exhausting can be accomplished by installing

Exhaust

Kit,

P/N

131456800,

available

through

your

parts

distributor. Follow the instructions supplied with the kit.

EXHAUST DUCT LOCATING DIMENSIONS

GAS SUPPLY REQUIREMENTS

A WARNING

Replace copper connecting pipe that is not

plastic-coated. Stainless steel or plastic-coated brass MUST

be used.

INSTALL MALE FITTINGS IN CORRECT DIRECTION

In installations where the exhaust system is not described in the

charts, the following method must be used to determine if the

exhaust system is acceptable:

1.

Connect an inclined or digital manometer between the

dryer and the point the exhaust connects to the dryer.

Set the dryer timer and temperature to air fluff (cool down)

and start the dryer.

Read the measurement on the manometer.

The system back pressure

MUST NOT be

higher than 0.75

inches of water column. If the system back pressure is less

1

Installation

MUST

conform with local codes, or in the absence

of local codes, with the National Fuel Gas Code, ANSI Z223.1

(latest edition).

The gas supply line should be of 1/2 inch (1.27 cm) pipe.

If codes allow, flexible metal tubing may be used to connect

your

dryer

to

the

gas

supply

line.

The

tubing

MUST

be

constructed of stainless steel or plastic-coated brass.

The gas supply line

MUST

have an individual shutoff valve.

A

1/8

inch

(0.32

cm)

N.RT

plugged

tapping,

accessible

for

test

gauge

connection,

MUST

be

installed

immediately

upstream of the gas supply connection to the dryer.

The dryer

MUST be

disconnected from the gas supply piping

system

during

any

pressure

testing

of

the

gas

supply

piping

system at test pressures in excess of 1/2 psig (3.45 kPa).

The dryer

MUST be

isolated from the gas supply piping system

during any pressure testing of the gas supply piping system at

test pressures equal to or less than 1/2 psig (3.45 kPa).

Advertising
This manual is related to the following products: