Electrical, Wiring connections, Table ii - recommended fusing and wiring data – Sears 390.2518 User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

ELECTRICAL

WIRING CONNECTIONS

A WARNING pjj^ hazard. Incorrect voltage can cause a fire or

seriously damage the motor and voids the warranty. The supply

voltage must be within ±10% of the motor nameplate voltage.

NOTICE: Dual-voltage motors are factorywired for 230 volts. If nec­
essary, reconnect the motor for 115 volts, as shown. Do not alter
the wiring in single voltage motors.

Install, ground, wire, and maintain your pump in compliance with

the National Electrical Code (NEC) or the Canadian Electrical Code

CCEQ, as applicable, and with all local codes and ordinances that
apply. Consult your local building inspector for code information.

Motor wires

connect here.

-Power supply wires

connect here.

230 Volt:

Connect 2 hot wires (black and red)

here and cap the white (neutrai) wire. It does
not matter which wire goes to which screw.

115 Volt:

Connect one hot wire (black or red)

to one of these screws (it doesn't matter
which one). Conned the white (neutral) wire
to the other screw. Cap any remaining

L-■ black or red wires.

Clamp the power cable to prevent strain
on the terminal screws.

■ Connect the green (or bare copper) ground wire

to the green ground screw.

Connection Procedure:

1. Connect the ground wire first as shown in Figure 9. The ground

wire must be a solid copper wire at least as large as the power
supply wires.

2. There must be a solid metal connection between the pressure

switch and the motor for motor grounding protection. If the
pressure switch is not connected to the motor, connect the
green ground screw in the switch to the green ground screw
under the motor end cover. Use a solid copper wire at least as
lai^e as the power supply wires.

3. Connect the ground wire to a grounded lead in a service panel,

to a metal underground water pipe, to a metal well casing at
least ten feet (3M) long, or to a ground electrode provided by
the power company or the hydro authority.

4.

Connect the power supply wires to the pressure switch as

shown in Figure 6.

5. Reinstall the pressure switch cover.

FIGURE 6 - Pressure switch wiring

TABLE II - RECOMMENDED FUSING AND WIRING DATA

Pump Model

Motor

Horsepower

Volts

Max. Load

Amperes

Branch

Delayed Fuse

Rating Amps

Distance in Feet From Motor to Meter

Oto

50

51 to

100

101 to

200

201 to

300

Wire Size

390.2514

1/2

115/230

10.5/5.2

15/15

14/14

14/14

10/14

8/14

390.2518

3/4

115/230

12.4/6.2

20/15

12/14

12/14

10/14

8/14

Advertising
This manual is related to the following products: