Carrier WEATHERMAKER 48/50AJ User Manual

Page 101

Advertising
background image

101

T705 (Limit Switch Thermistor Failure) — A failure (the sen-

sor is outside the range of –40 F to 240 F) of this thermistor

(Temperatures

AIR.T

S.G.LM) will cause an alert to occur

and a disabling of the limit switch monitoring function for the

staged gas control board (SCB). Recovery is automatic.

Reason for failure may be due to faulty wiring, a faulty

thermistor, or a damaged input on the staged gas control board

(SCB).

MAJOR SYSTEM COMPONENTS

General —

The 48/50A Series package rooftop units with

electric cooling and with gas heating (48A units) or electric

cooling and electric heating (50A units) contain the

ComfortLink™ electronic control system that monitors all

operations of the rooftop. The control system is composed of

several components as listed below. See Fig. 15-23 for typical

control and power component schematics. Figures 24 and 25

show the layout of the control box, unit, and thermistor and

transducer locations.

Factory-Installed Components

MAIN BASE BOARD (MBB) — See Fig 26. The MBB is

the center of the ComfortLink control system. The MBB con-

tains the major portion of the operating software and controls

the operation of the unit. The MBB has 22 inputs and 11 out-

puts. See Table 115 for the inputs and output assignments. The

MBB also continuously monitors additional data from the

optional ECB1, ECB2, SCB, and CEM boards through the

LEN communications port. The MBB also interfaces with the

Carrier Comfort Network

®

system through the CCN communi-

cations port. The board is located in the main control box.
ECONOMIZER BOARD (ECB1) — The ECB1 controls the

economizer actuator and the power exhaust fans. The ECB1

operates the economizer motor using a digital communication

signal that also provides status and diagnostics for the econo-

mizer motor. See Fig. 27. The ECB1 also controls the operation

of the power exhaust motors and provides up to 6 stages of dig-

itally sequenced power exhaust either based on the economizer

motor position or the building pressure. The board has 4 inputs

and 6 outputs. Additionally, ECB1 provides an output that will

send a 4 to 20 mA signal to a field-installed VFD power ex-

haust accessory. Details can be found in Table 116. The ECB1

board is located in an auxiliary box located at the end of the

unit behind the filter access door. The board also contains

a second LEN port than can be used with the accessory

Navigator™ display.

VAV BOARD (ECB2) — The VAV board (which is the same

hardware as the ECB1) is used to control the supply fan on

VAV units. See Fig. 27. It sends a 4 to 20 mA signal to the VFD

based on a supply duct pressure sensor connected to the board.

The board also accepts a signal from another pressure sensor

that monitors building pressure and controls the operation of

the optional modulating power exhaust motors. The board will

also be used on CV units with the optional building pressure

control feature and modulating power exhaust. This board is

also used to control a digitally controlled hot gas bypass sole-

noid with an integral orifice for use in low load applications.

This board is located in the auxiliary control box. Input and

output assignments are summarized in Table 117.
STAGED GAS HEAT BOARD (SCB) — When optional

staged gas heat is used on CV and VAV units, the SCB board is

installed and controls operation of the gas valves. See Fig. 28.

The SCB also provides additional sensors for monitoring of the

supply-air temperature. This board is located in the gas heat

section of the unit. The inputs and outputs are summarized in

Table 118.
CONTROL EXPANSION MODULE (CEM) — The optional

CEM (also available as an accessory) is used to accept inputs

for additional sensors or control sequence switches, including:
• smoke control mode field switches

• VAV Supply Air Temperature Set Point reset using an exter-

nal 4 to 20 mA signal

• outdoor air CO

2

sensor (for supply duct pressure reset using

an eternal 4 to 20 mA signal)

• external fan status pressure switch input (CV units)

• demand limit sequence proportional signal or discrete

switches
The CEM board is located in the main control box. See

Fig. 29. The inputs and outputs are summarized in Table 119.
INTEGRATED GAS CONTROL (IGC) — One IGC is pro-

vided with each bank of gas heat exchangers (2 used on the size

020-050 units and 3 on size 051 and 060 units). The IGC

controls the direct spark ignition system and monitors the

rollout switch, limit switches, and induced-draft motor Hall

Effect switch. The IGC is equipped with an LED (light-

emitting diode) for diagnostics. See Table 120.
COMPRESSOR PROTECTION BOARD (CS) — This board

monitors the status of the compressor by sensing the current

flow to the compressors and then provides digital status signal

to the MBB.