Compensated Start section for more information. A setting of

0 minutes indicates Temperature Compensated Start in Cooling

is not permitted.
Temperature Compensated Start Heating Factor (TCS.H) —

This factor is used in the equation of the Temperature Compen-

sated Start Time Bias for heating. Refer to the Temperature

Compensated Start section for more information. A setting of

0 minutes indicates Temperature Compensated Start in Heating

is not permitted.
Fan Fail Shuts Downs Unit (SFS.S) — This configuration

will determine whether the unit should shut down on a supply

fan status fail or simply alert the condition and continue to run.

If set to YES, then the control will shut down the unit and send

out an alarm if supply fan status monitoring fails. If set to NO,

the control will not shut down the unit if supply fan status mon-

itoring fails but the control will send out an alert.
Fan Status Monitoring (SFS.M) — This configuration selects

the type of fan status monitoring to be performed.
0 - NONE — No switch or monitoring
1 - SWITCH — Use of the fan status switch
2 - SP RISE — Monitoring of the supply duct pressure.
VAV Unoccupied Fan Retry Time (VAV.S) — Machine con-

trol types 1 and 2 (VAV-RAT,VAV-SPT) monitor the return-air

temperature during unoccupied periods to determine if there is

a valid demand for heating or cooling before initiating an unoc-

cupied heating or cooling mode. If the routine runs but con-

cludes a valid demand condition does not exist, then the pro-

cess is not permitted for the period of time defined by this con-

figuration. Reducing this value allows a more frequent re-

sampling process. Setting this value to zero will prevent any

sampling sequence.
Unit Size (SIZE) — There are several unit sizes (tons) for the

A Series control. Make sure this configuration matches the size

called out by the model number of the unit. This is important as

the cooling stage tables are directly determined based on this

configuration.

Discharge Pressure Transducers (DP.XR) — This configuration

configures the unit for use with discharge pressure transducers.

The 48/50A2,A3,A4,A5 units will be automatically configured

for discharge pressure transducers and DP.XR should be set to

Yes.

Suction Pressure Transducer Type (SP.XR) — This configu-

ration specifies the type of suction pressure transducer that is

being used. Set SP.XR to 0 for support of a pressure transducer

with a range of 0 to 135 psig. Set SP.XR to 1 for support of a

pressure transducer with a range of 0 to 200 psig.
NOTE: The 48/50A2,A3,A4,A5 units do not require a change

to the SP.XR factory default setting.
Refrigerant Type (RFG.T) — This configuration specifies the

type of refrigerant used in the unit. Configuration RFG.T is set

to 0 if the refrigerant used is R-22. Configuration RFG.T is set

to 1 if the refrigerant used is R-410A. Do not change this

setting.
Condenser Type (CND.T) — This configuration specifies the

type of condenser installed in the unit. Configuration CND.T is

set to 0 if the condenser is a round tube, plate fin coil (RTPF).

Configuration CND.T is set to 1 if the condenser is a micro-

channel heat exchanger coil (MCHX).
MAT Calc Config (MAT.S) — This configuration gives the

user three options in the processing of the mixed-air tempera-

ture (MAT) calculation:
MAT.S = 0

There will be no MAT calculation.

MAT.S = 1

The control will attempt to learn MAT over time. Any time

the system is in a vent mode and the economizer stays at a

particular position for long enough, MAT is set to equal

EDT. Using this, the control has an internal table whereby it

can more closely determine the true MAT value.

MAT.S = 2

The control will not attempt to learn MAT over time.
To calculate MAT linearly, the user should reset the MAT

table entries by setting MAT.R to YES. Then set MAT.S = 2.

The control will calculate MAT based on the position of the

economizer, outside-air temperature, and return-air

temperature.
To freeze the MAT table entries, let the unit run with MAT.S

= 1. Once sufficient data has been collected, change MAT.S

= 2. Do not reset the MAT table.

Table 43 — Unit Configuration

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULTS

UNIT

UNIT CONFIGURATION

C.TYP

Machine Control Type

1 - 6

CTRLTYPE

4

CV.FN

Fan Mode (0=Auto, 1=Cont)

0 - 1

FAN_MODE

1

RM.CF

Remote Switch Config

0 - 3

RMTINCFG

0

CEM

CEM Module Installed

Yes/No

CEM_BRD

No

TCS.C

Temp.Cmp.Strt.Cool Factr

0 - 60

min

TCSTCOOL

0

TCS.H

Temp.Cmp.Strt.Heat Factr

0 - 60

min

TCSTHEAT

0

SFS.S

Fan Fail Shuts Down Unit

Yes/No

SFS_SHUT

No

SFS.M

Fan Stat Monitoring Type

0 - 2

SFS_MON

0

VAV.S

VAV Unocc.Fan Retry Time

0 - 720

min

SAMPMINS

50

SIZE

Unit Size (20-60)

20 - 60

UNITSIZE

20

DP.XR

Discharge Press. Transducers

Yes/No

DP_TRANS

No

SP.XR

Suct. Pres. Trans. Type

0 - 1

SPXRTYPE

0

RFG.T

REFRIG: 0=R22, 1=R410A

0 - 1

REFRIG_T

Unit dependent

CND.T

CND HX TYP: 0=RTPF, 1=MCHX

0 - 1

COILTYPE

Unit dependent

MAT.S

MAT Calc Config

0 - 2

MAT_SEL

1

MAT.R

Reset MAT Table Entries?

Yes/No

MATRESET

No

MAT.D

MAT Outside Air Default

0-100

%

MATOADOS

20

ALTI

Altitude……..in feet:

0 - 60000

ALTITUDE

0

DLAY

Startup Delay Time

0 - 900

sec

DELAY

0

STAT

TSTAT-Both Heat and Cool

Yes/No

TSTATALL

No

AUX.R

Auxiliary Relay Config

0 - 3

AUXRELAY

0

SENS

INPUT SENSOR CONFIG

SPT.S

Space Temp Sensor

Enable/Disable

SPTSENS

Disable

SP.O.S

Space Temp Offset Sensor

Enable/Disable

SPTOSENS

Disable

SP.O.R

Space Temp Offset Range

1 - 10

SPTO_RNG

5

RRH.S

Return Air RH Sensor

Enable/Disable

RARHSENS

Disable

FLT.S

Filter Stat.Sw.Enabled ?

Enable/Disable

FLTS_ENA

Disable