Bryant PAYNE 619C User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Normal Operation — When the temperature of the room is

6° P above the selected temperature, the compressor and

outdoor fan will operate for 8 minutes. The indoor fan will

operate in low speed. If the room temperature is above the

selected temperature, but not by more than 6° F, the com­

pressor and outdoor fan operate for 4 minutes. The indoor

fan will run at low speed and will stop 30 seconds after the

compressor stops. After 3 minutes, the indoor fan runs at

low speed for 30 seconds. The normal dehumidification op­

eration is repeated for the new room temperature.

When the room temperature is within 4° F below the se­

lected temperature, the system operates for 8 minutes. The

compressor and outdoor fan operate for 3V2 minutes. The

indoor fan will operate at low speed and will stop 30 sec­

onds after the compressor stops. After 3 minutes, the in­

door fan starts in low speed for one minute. The normal

dehumidification operation is repeated for the new room

temperature.

If the room temperature is 4° F below the selected temper­

ature, the compressor, outdoor fan, and indoor fan remain

off. After 3 minutes, the indoor fan operates at low speed

for one minute. This is repeated until 8 minutes have elapsed.

The normal dehumidification operation is repeated for the

new room temperature.

HEAT PUMP Heating Mode (Heat Pump Systems Only)

— When the HEAT PUMP mode is selected, the indoor fan

will operate continuously at the selected speed if the speed

is high, medium, or low. If the indoor fan is in auto oper­

ation, the fan will change operating speeds depending on

the room temperature. The electric heat is off and the re­

versing valve will be on. The compressor cannot run for 3

minutes from the time the system starts up or for 3 min­

utes from the time it last operated. When the temperature

of the room is 8° F below the selected temperature, the unit

will operate in HEAT PUMP mode until the temperature

is F above the selected temperature. If the temperature

of the room is between 2° F and 8° F below the selected

temperature, the unit operates in HEAT PUMP mode un­

til the selected temperature is reached.

In the HEAT PUMP mode, the compressor and outdoor fan

will operate until the room temperature has reached the

temperature indicated above. The indoor fan will remain

off until the discharge temperature of the fan coil is 86 F.

The fan will then operate in low speed until the discharge

temperature is 98 F. Then the fan will operate at high speed

if the room temperature is 4° F or more below the selected

temperature. The indoor fan will run at medium speed when

the room temperature is between 2° F and F below the

selected temperature. The indoor fan will operate at low

speed if the room temperature is within 2° F of the se­

lected temperature. When the heating demand is satisfied,

the compressor and outdoor fan will stop and the indoor

fan will operate until the discharge air temperature is

77 F. The fan will turn off for 3 minutes, then turn on for

one minute — this will be repeated until heating is again

required.

' MAXIMUM HEATING Mode (Heat Pump Systems Only)

— This mode of operation is the same as the HEAT PUMP

heating mode, except that electric heat is used to assist the

heat pump.

• ELECTRIC HEATING Mode (Heat Pump Systems Only)

— The indoor fan operation is the same as the HEAT PUMP

mode, except that electric resistance heating only is used.

• AUTOMATIC OPERATION Mode - AUTOMATIC OPER­

ATION mode runs the system in cooling or heating at 2° F

above the selectéd temperature for cooling and 2° F below

the selected temperature for heating. In the temperature

range between heating and cooling, only the fan will oper­

ate. A minimum of 10 minutes is required between a change

from heating to cooling or from cooling to heating.

• DEMAND DEFROST Mode (Heat Pump Systems only) —

This unit uses a demand defrost system to remove frost

from the outdoor coil during heating operation. The indoor

fan and outdoor fan are shut off during defrost. For com­

plete description of defrost operation, see the controls, ser­

vice and troubleshooting guide sections of the duct-free

systems manual, available from your distributor.

• SLEEP Mode — The SLEEP mode timer will turn the unit

off when the timer reaches zero minutes. During the first

IV

2

hours from the time the SLEEP mode timer starts, the

room temperature is set back from the selected tempera­

ture a total of 4 F in cooling and 6 F in heating.

• AWAKE Mode — The awake timer will turn the unit on

when the timer reaches zero minutes. The unit will start

in the same mode and at the same selected temperature as

when the system shut off.

NOTE:

The system can be programmed for the sleep mode

or the awake mode, but it cannot be programmed for both of

these modes simultaneously.

CLEANING AND MAINTENANCE

For proper system operation we recommend that the clean­

ing and maintenance operations in Table 6 be performed.

I. LUBRICATION

The indoor-fan motor, automatic air sweep motor, and the

outdoor fan motor are factory lubricated and require no

oiling.

-

12

-

Advertising