Bryant PAYNE 619C User Manual

Page 3

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

II. SELECT LOCATION

Consult local building codes and NEC for special installation

requirements.

There are several ways the unit may be installed to different

types of ceiling construction. These instructions do not cover

all installation methods. As a typical installation, these in­

structions focus primarily on mounting the unit to metal in

new construction. Plan your installation carefully before you

begin. Listed below are some guidelines that should be fol­

lowed when determining location for the unit.

1. Place unit adjacent to an outside wall if fresh air is re­

quired, ensuring that location allows for complete air

distribution.

2. Determine a convenient and accessible location to mount

the wired remote controller. Note that because the con­

troller is not used to sense room conditions, it is not nec­

essary to consider this factor when determining the

controller location.

The controller cable can be routed through walls and does

not need to be surface mounted. For additional informa­

tion on remote controller, see separate controller kit in­

stallation instructions.

3. Allow sufficient space for airflow clearance, wiring,

refrigerant piping, and servicing unit (Fig. 3).

4. Make sure the unit is easily accessible to electrical power.

5. Run refrigerant piping as directly as possible, avoiding

any unnecessary turns or bends.

6. Condensate piping can be directed through the inside

wall to an approved drain, or directed straight outside.

NOTE:

The piping hole for condensate line must slope at a

minimum pitch of 1 in. per 10 ft to ensure proper drainage. If

proper pitch cannot be achieved, install accessory conden­

sate pump at this time.

NOTE;

The accessory condensate pump should be installed

before hanging the unit.

III. MOUNT UNIT

Refer to Fig. 6 for clearances and dimensions. Use mounting

template included inside box to locate mounting bolt holes,

piping holes, electrical connections, and accessory outdoor-

air intake, if used.

Select proper type of hardware from the guidelines below. See

Fig. 4.

Wooden Structure

Install hanging bolts on a square wooden piece placed over

beams.

Newly Built Concrete Slab

Install hanging bolts with inserts, embedded bolts, etc.

Metal Structure

Install hanging bolts utilizing an existing angle or by install­

ing a new support angle.

Previously Built Concrete Slab

Install hanging bolts with expansion anchor.

A. To Mount Unit:

1. Remove mounting bracket and reinstall the 2 hex-head

bolts (factory supplied) into each side of indoor unit as

shown in Fig. 5. Allow approximately 3/8-in. space be­

tween bolt head and unit.

2. Determine installation position, paying particular at­

tention to piping lengths and wiring connections, clear­

ances, etc. See Fig. 3 for connection locations. Fig. 6 for

clearances, and Fig. 7 and 8 for bolt locations.

3. Open knockout if right-side piping connections are re­

quired (Fig. 9).

4. Cut the slit portion in rear of the side panel with a saw

or cutter knife. (Fig. 9).

If indoor unit accessory louver guard is to be installed, in­

stall at this time and refer to installation instructions pack­

aged with this accessory.

5. Mount hanging brackets on ceiling (Fig. 10) for either

concealed or exposed bolt hanging position.

6. Lift the unit into place, and fit the hex-head bolts on

sides of indoor unit into slit grooves of mounting brack­

ets (Fig. 11). Ensure unit is mounted level to assure proper

drainage.

7. Tighten bolts securely.

IV. CONNECT REFRIGERANT PIPING

Fan coil units may be connected to condensing units using

field-supplied refrigerant grade piping. Refer to Table 3 for

the correct size piping. The length of refrigerant pipe de­

pends on the unit placement and building structure; keep in

mind to run pipes as directly as possible. For piping require­

ments over 50 ft of total run, or more than 25 ft of lift, con­

sult the long line application guidelines available from your

distributor.

Use the following instructions to connect piping.

1. Install insulation. Insulate all refrigerant lines on heat

pumps to prevent condensation. It is extremely impor­

tant that all refrigerant lines and the Check-Flo-

Rater"' metering device be insulated on heat pumps. On

cooling only units, the liquid line may be left uninsu­

lated. Use any acceptable heat resistant closed-cell foam

insulation (minimum 3/8-in. wall thickness). When in­

sulating piping, cap ends and slide insulation over the

piping. Insulation can also be cut and placed over

piping.

2. Run liquid and gas refrigerant piping.

a. Run pipes as directly as possible, avoiding any un­

necessary turns and bends.

b. Suspend refrigerant pipes so that the insulation is

not damaged and vibrations are not transmitted to

the structure.

c. Leave slack in the refrigerant pipe between the struc­

ture and the unit to absorb vibrations.

d. Install flare connection on tubing to liquid line at fan

coil (Fig. 12). The correct piston size is shipped in ths

Check-Flo-Rater body with 619C units. If you have

any questions, use Table 4 to determine required pis­

ton size for the system being installed. The arrow on

the metering device body must face away from the

indoor coil.

-

3

-

Advertising