Low-voltage wiring, Limit control, Thermostat location – Bryant 394 Gas User Manual

Page 4: Iii. electrical connections, Line-voltage wiring

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

I

TO HEATING AND
COOLING CONNECTIONS
OF THERMOSTAT
P/N 34427D030
a 34427D031

\ TO CONDENSER

> CONTACTOR COIL

I

CONNECTIONS

A68367

Figure 2 - Control Box, Cover Removed,

No Internal Wiring Changes

TO HEATING AND
COOLING CONNECTIONS

VOF THERMOSTAT
^P/n 34427D030

a 34427D031

] TO CONDENSER

I LOW VOLTAGE
(^LEAD OR

j TERMINAL STRIP

NOTE-'

WIRE WITH* IN FIGURE 2 IS

REMOVED, AND DISCARDED WHEN

A68368 CONDENSEFTHAS TRANSFORMER.

Figures 3 - Control Box, Cover Removed,

Showing Internal Wiring Changes

Low-Voltage Wiring

Field low-voltage connections are made at the low-
l^oltage terminal strip. See Figure 6 for heating only.
For Model

394

Furnaces used in conjunction with

slectric or gas air conditioning units that do not have

4n integral transformer, see Figure

2.

If the

394

Fur-

fiace is used in conjunction with an electric or gas air
jonditioning unit having an integral transformer, see
Figure

3.

Figure

3

shows a field-installed wire running from one

side of the air conditioning transformer, through the

4ole marked “F” in the terminal strip to the blower

relay in the control box for the Model

394

Furnace.

The wire marked * in Figure

2

is removed from the

:ontrol box and discarded.

Limit Control

This control shuts oflF the gas and energizes the blower
notor if the furnace becomes overheated.
The recommended method of checking the limit control

s to gradually block off the return air after the furnace

,ias been operating for a period of at least five minutes.

\s soon as the limit has proven safe, the return air
opening would be unblocked to permit normal air
jirculation. By using this method to check the limit

control, it can be established that the limit is function-

ng properly and will “fail-safe” if there is a motor
ailure.

Thermostat Location

The room thermostat should be located where it will
re in the natural circulating path of room air. Avoid

locations where the thermostat would be exposed to
cold air infiltration, drafts from windows, doors, or
other openings leading to the outside, or exposure to
air currents from warm or cold air registers; or to ex­
posure where the natural circulation of the air is cut
off—such as behind doors, above or below mantels,
shelves, etc.

The thermostat should not be exposed to heat from
nearby radiators, fireplaces, radios, televisions, lamps,
or rays from the sun. Nor should the thermostat be
mounted on a wall containing pipes or warm air ducts,
or a flue or vent which could affect its operation and

prevent it from properly controlling the room tempera­
ture. Any hole in the plaster or panel through which
the wires pass from the thermostat should be adequately

sealed with suitable material to prevent drafts from

affecting the thermostat.
The heat anticipator on the thermostat should be set
at 0.8 amps.

III. ELECTRICAL CONNECTIONS

Line-Voltage Wiring

All electrical connections are to be made in accordance
with the local electrical codes. A permanent, live,
separately fused electric power supply, complete with
manual switch, should be provided for the furnace.
Field wiring connections should be made in accordance

with the unit wiring diagrams.

-

4

-

Advertising