V. coil connections, Vi. electrical connections – Bryant Outdoor Heating Unit 379A User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Figure 4—Mounting Air Shroud on Propane Unit

An air shroud is also shipped with propane units only.
Install these items as follows:

1. Remove the cover from the vent opening on the

unit.
2. Remove the top plate from the vent cap assembly

(held by 4 sheet metal screws).
3. Use the screws supplied with the assembly to fasten

the base section of the vent cap assembly to the top
cover of the unit (the unit top is predrilled to receive
the screws).

4. Reattach top plate removed in step 2.
5. Remove the 3 self-tapping screws located ap­
proximately 7 inches behind the vent cap. Use these

screws to attach the sheet metal angle to the unit top
cover at this location.
6. Use the screws enclosed in the air shroud package

to mount the air shroud as shown in Figure 4
(propane units only).

V. COIL CONNECTIONS

Figure 5 is a rear view photo of a partially disassem­

bled Model 48W-379A unit.
The coil location and chilled water connections for

both the 48W- and 60W-379A are the same for both
units. These two models differ only in the size of the
factory installed chilled water coil.

Two 2-3/8-inch diameter holes are provided in the
right rear corner panel for the chilled water piping en­
trance to the unit.

NOTE: Two packaged vinyl grommets are shipped
loose in the blower compartment. Insert one grommet

in each of the 2-3/8-inch corner panel holes.
Route the chilled water piping through the two grom­
mets and connect to the two 1-inch F.P.T. connectors

on the coil header. Refer to Figure 5 for chilled water

inlet and outlet connections.

CHILLED WATER
CONNECTIONS

1 /

IN OUT

BELT TENSION

ADJUSTING SCREW ■

BLOWER MOTOR

TRANSFORMER

POWER
CONNECTIONS
TAG

OILING
LABEL

CONDENSATE

DRAIN CONNECTION

Figure 5—Rear View of Partially

Disassembled 48W -379A

Refer to the chiller installation instructions for per­
tinent information concerning type and size of piping,,

length of pipe permissible, type of freeze protection,

and chilled water additive required.

VI. ELECTRICAL CONNECTIONS

CAUTION: Before proceeding with the electrical con­
nections, check the power supply to be sure that the

voltage, frequency, and phase correspond to that

specified on the unit rating plate.

All electrical connections are to be made in ac­
cordance with the National Electrical Code and the

39379D36

-4-

Advertising