STOVE PLACEMENT:

Stove must be placed so that no combustibles are within, or can swing within (i.e. drapes doors),
36” of the heater.

If the stove is placed in a location where the ceiling height is less than 7’, it must follow the
requirements in the section “Alcove Installation”.

Stove and floor protection must be installed on a level secure floor

FLOOR PROTECTION REQUIREMENTS:

The stove must be installed on a non-combustible floor protector (i.e. sheet steel with cement, tile or
slate) extending the full width and depth of the stove and extending 6” in front of the stove. Floor
protector needs to be a minimum of 24.5” deep X 30.5” wide and must be a minimum of .018” thick
(26 gauge).

Must extend under and 2” to each side of chimney tee (if used).


MINIMUM CLEARANCES TO COMBUSTIBLES

(FIGURES 10 – 15)

1” From Back Of Heater To Combustibles

3” From PL Vent to Combustibles

2” From Side of Heater to Combustibles

1” From Back Corner of Heater to Combustibles

6” Non Combustible Surface In Front Of Heater

16” From Top Of Heater to Combustibles

36” to drapes, doors, anything that can swing