TROUBLESHOOTING AND REPAIR

31

13. Inspection of Drain Switch

Check for continuity between terminals 1 and 2.
Continuity should exist. With switch depressed,
continuity should not exist between terminals 1
and 2. If continuity is not as specified above,
replace the switch.

14. Inspection of Fan Motor

Measure resistance across the terminals of the
fan motor.

Terminals (at 77˚F (25˚C))
J6 - CF1

Approx. 6.8

J5 - CF1

Approx. 10.5

CF1 - CF2 Approx. 19.0

If the measured resistance is not equal to these
standard values, replace the fan motor.

15. Inspection of Compressor Motor

Measure resistance across the terminals of the
compressor motor.

Terminals (at 77˚F (25˚C ))

R - C

Approx. 0.94

C - S

Approx. 1.96

S - R

Approx. 2.90

If the measured resistance is not equal to these
standard values, replace the compressor. The
compressor has a built-in overload relay. The
overload relay should be operational if the above
resistance is obtained under normal temperature.

2

NC

C

1

DS2

DS1

To J103

DRAIN

SWITCH

TOP OF

BASE

PLATE

Inspection of Drain Switch

Inspection of Compressor Motor

CF1 (White)

CF2 (Brown/White)

J5 Low (Red)

J6 High (Black)

Ground

(Green/Yellow)

Inspection of Fan Motor