Physical

Product dimensions ( 1U )

442 x 270 x 43.5 mm ( W x D x H )

Packing dimensions ( 1U )

530 x 380 x 80 mm ( W x D x H )

Net weight

4.6 kg / 10.1 lb

Gross weight

5.1 kg / 11.2 lb

Product dimensions ( 2U )

442 x 270 x 87.5 mm ( W x D x H )

Packing dimensions ( 2U )

530 x 380 x 140 mm ( W x D x H )

Net weight

6.5 kg / 14.3 lb

Gross weight

7 kg / 15.4 lb

Chassis color / materials

Dark / Steel

Electrical

Nominal input voltage

208V

Acceptable input voltage

±10% nominal

Input frequency

50 / 60Hz

Inlet plug & cord

2 x L6-20P plug with 3-meter cord

Outlet connectors

Multiple C13 / C19 outlets

Local meter

3-digital LED current meter

Overload protection

1 x 20-amp circuit breaker

Transfer time

25ms maximum

Electrical endurance

1 x 10

5

operations

Power consumption

Approx. 8VA

Environmental

Operating temperature

-5 to 45°C degree ( 23 to 113°F )

Storage temperature

-25 to 65°C degree ( 13 to 149°F )

Operating humidity

0~95%, non-condensing

Storage humidity

0~95%, non-condensing

Compliance

EMC

FCC & CE certifi ed

Safety

LVD certified

Environment

RoHS2 & REACH compliant