WATER LEVEL

29” TO FLOOR

Steam Side Control - Two low water cutoff devices and

two pressuretrols, one with auto reset and the second with

manual reset, are required. In order to make the two

low water cutoff devices work in the appropriate

sequence, manufacture recommends locating both

devices at same end of boiler.
There are three different control systems for three different

types of condensate returns.
Identify the three different types of condensate returns:

• Gravity return - condensate is returned by gravity.
• Condensate pump return - condensate is returned

by pump(s), controlled by the water level in the

condensate receiver tank.

• Boiler Feed Pump Return - condensate is returned by

pump(s), controlled by the water level in the boiler.

Normal

Water Line

STEAM SIDE CONTROLS

Figure 2 - Steam Boiler Feed Pump Return

Figure 3 - Steam Gravity and Condensate Pump Return

Gravity Return And Condensate Pump Return
With gravity and condensate pump return, additional

control components are the same. See Table #5a and

Figure #2 for tappings.

• Tappings B & B location shown in Figure #2.

Installation shown in Figure #3, Primary LWCO and

Pressuretrol with gauge glass set.

• Tappings D or F (Figure #2)- Manual reset pressuretrol

and ¼” 90° brass syphon.

• Tappings E & F - Secondary LWCO (w/manual reset).

Use in conjunction with primary LWCO equipped on

boiler.

When using two LWCOs, place manual reset lower than

automatic LWCO. Water must be visible in gauge glass

when manual reset trips.

• Figure 3 shows how to raise automatic (Series 67)

LWCO 1-inch.

• Remove 1” from long side of ¼” diameter 90° brass

siphon tube.

• Remove nipple in series 67 and replace with 1 ½” long

nipple and street elbow.

• Water level control device located on condensate

receiver tank and controls condensate return pump is

not supplied.

Table #5a: CSD-1 Steam Trim Carton Material List for Gravity Return

or Condensate Pump Return (Part No. 41257103)

Item

Description

Part No.

Qty.

1

LWCO w/Manual Reset (secondary)

240007388

1

2

Bushing, Steel or Cast 1” x 1¼”

14657016

1

3

Pressure Switch Control, Manual Reset

14662311

1

4

90° Brass Syphon, ¼”

14643004

1

5

ELB,ST,1/2”,45 DEG.BRASS

240007541

1

6

NIPPLE 1/2” X 1/2”LG BRASS

240007542

1

5