Y – download neuron executable, Performance test, 23). if you p – Echelon NodeUtil Node Utility User Manual

Page 29

Advertising
background image

NodeUtil User’s Guide

23

generated XIF file with any Echelon or third-party LNS tool, including the

LonMaker Integration Tool.

If output redirection is in effect, the current output file is closed before creating

the XIF file.

Y – Download Neuron Executable

Use this command to download a Neuron application image file to the selected
device. You can specify an application image file (.ndl or .nxe extension) that is

generated by the NodeBuilder FX Development Tool or Mini FX application. If

the device already contains an alphanumeric application ID, this name is the
default for the application image file name.
Recommendation: Use a .ndl file for downloading the device application. A .ndl
file contains the application code and initial values for configuration network

variables, whereas a .nxe file contains the application code only.
If the download is successful, you are asked if you want to set the device
configured, online. Answer “yes” to this question only if the device already

contains a valid network configuration for this application. By default, the device

will be set to the unconfigured state. After setting the state, NodeUtil reads the
state of the device and displays any errors.
For .nxe files, the Y command does not check that the application image file that

you are loading is compatible with the device hardware configuration. The Y
command does perform compatibility checking for .ndl files. Thus, before loading

an application to a device using a .nxe file, verify that the application image file

was linked using the correct device model and firmware version for your target
device. For FT 3150 or PL 3150 devices, also verify that the application image

file was linked using the correct memory map for the device.

If an incompatible application image file is loaded to a device, the device

generally performs continuous watchdog resets. You might be able to recover it

by downloading a compatible application image file. However:

• If the device is based on an FT 3120, PL 3120, or PL 3170 Smart

Transceiver, it might not be recoverable.

• If it is based on an FT 3150 or PL 3150 Smart Transceiver, you can use

the EEBLANK program (available from the Echelon Web site) to blank

the EEPROM and reboot the default image.

• If it is based on an FT 5000 Smart Transceiver or Neuron 5000 Processor,

you might be able to recover it by clearing the external non-volatile
memory for the device. See the

Series 5000 Chip Data Book

for a

description of how to clear the external non-volatile memory.

If you attempt to set the device to the configured state after loading, but the
device does not contain a valid network configuration for this application, then

the Neuron firmware detects a configuration checksum error and sets the device

to be unconfigured.

[

– Performance Test

Use this command to test the performance of the channel and the device.

You are prompted to provide the following information:

Advertising