Network interfaces overview – Echelon LonScanner FX Protocol Analyzer User Manual

Page 66

Advertising
background image

60

Network Interfaces

Network Interfaces Overview

You can use any of the following Echelon network interfaces with the

LonScanner FX Protocol Analyzer:

ƒ

U10 USB Network Interface

and

U20 USB Network Interface

L

ON

W

ORKS

network interfaces for any computer with a USB interface,

which includes most desktop, laptop, and embedded computers. These

network interfaces are ideal for use in applications that require a

computer to monitor, manage, or diagnose a network. The interfaces

feature support for TP/FT-10 channels (the U10) or PL-20 channels (the

U20), and provide simple plug-and-play installation. See the

LonWorks

USB Network Interface User's Guide

(078-0296-01B) for more

information about the USB network interfaces.

ƒ

PCLTA-20/SMX PCI Network Interface

and

PCLTA-21 PCI Network

Interface

— L

ON

W

ORKS

network interfaces for desktop and embedded

personal computers equipped with a 3V (PCLTA-21) or 5V (both PCLTA-

20 and PCLTA-21) 32-bit PCI interface. These network interfaces are

ideal for use in applications that require a desktop or embedded computer

to monitor, manage, or diagnose a network. There are four versions of

the PCLTA-21 card that include an onboard transceiver (TP/FT-10,

TP/XF-78, TP/XF-1250, or TP-RS485), and one version of the PCLTA-20

card that accepts a standard modular transceiver (SMX) which can be

used with any media type for which an SMX transceiver exists. Before

using either a PCLTA-20 or a PCLTA-21 with the protocol analyzer, you

must configure it to operate as a layer-2 network interface. For

instructions, see

PCC-10 and PCLTA-20/21

on page 61.

ƒ

PCC-10 PC Card

— L

ON

W

ORKS

network interface for any computer

equipped with a type II PC card (formerly PCMCIA) interface, which

includes most laptop computers. Includes an integral TP/FT-10

transceiver for use with TP/FT-10 channels. Other transceiver types can

be connected to the PCC-10 through external transceiver pods. Before

using a PCC-10 with the protocol analyzer, you must configure it to

operate as a layer-2 network interface. For instructions, see

PCC-10 and

PCLTA-20/21

on page 61.

ƒ

i.LON SmartServer

— Controller, Web server, and L

ON

W

ORKS

remote

network interface (RNI) that can be accessed through an Ethernet or

dial-up IP connection, with optional IP-852 routing support. This

network interface is ideal for use in applications requiring remote access

via a LAN or the Internet and allows you to remotely monitor a network

with the LonScanner tool. The LonScanner tool can either be used with

the remote network interface (RNI) capability of the

i

.LON products, or

with an IP-852 channel created using the optional IP-852 routing of the

i

.LON products. LonScanner IP-852 support requires an LNS Turbo

Server. The LonScanner tool is also compatible with the original

i

.LON

SmartServer and all versions of the

i

.LON 100 Internet Servers. See the

i.LON SmartServer 2.0 User's Guide

(078-0345-01E) for more

information about the

i.

LON SmartServer, including how to configure it

as an RNI or an IP-852 router. If you are using an earlier version of the

i

.LON product, see the user’s guide for the version that you are using.

Advertising