IsiUpdateUserInterface() and IsiDiagnostics() calls on the remote device.

Consult the ISI Programmer’s Guide for more information on these calls.

You can also manually change the Mini computer’s network interface subnet

and node IDs by following these steps:

1. Click Change Subnet/Node ID. This opens the dialog shown in

Figure 3.5.

Figure 3.5 Change Subnet/Node ID Dialog

2. Enter the subnet ID in the Subnet ID box, and the node ID in the

Node ID box. If the device you are monitoring is on a power line
channel (such as a PL Evaluation Board), the subnet ID must be in

the range of 128 – 192. If the device you are monitoring is on a
TP/FT-10 channel (such as an FT Evaluation Board), the subnet ID

must be in the range of 64 – 125. In most cases, each subnet supports

up to 127 devices. However, node IDs 126 and 127 are reserved for
managed tool use, so the node ID you enter must be in the range of 1

– 125.

3. Click OK to save and apply the change.

Mini EVK User’s Guide