Figure 3a: typical channel board, Caution, Table 4: potentiometers per channel – ENMET MX-48 User Manual

Page 11

Advertising
background image

MX48 C

ONTROL

ENMET Corporation

7

Figure 3a: Typical Channel Board

See Figure 1 for location of Channel Boards within

MX48 C

ONTROL

enclosure.

For channels 5 through 8 on second Channel Board:

Channel 1 = Channel 5

Channel 2 = Channel 6

Channel 3 = Channel 7

Channel 4 = Channel 8

Display Potentiometers

Caution:

Each channel display is adjusted at the factory and should not need to be readjusted. Any alignment

should be adjusted at the sensor/transmitter. Table 4 provides the function of

MX48 C

ONTROL

potentiometers if adjusted by mistake.

Table 4: Potentiometers per Channel

Left /2

O =

Control display

ZERO

potentiometer

S =

Control display span potentiometer

Right /2

4 =

potentiometer 4 mA / current output

20 =

potentiometer 20 mA / current output (for full scale)

Fuse

Fuse

Fuse

Fuse

Fuse

Display POTs for

Channel 1 or 5

see Caution

Channel 3 or 7

Channel 4 or 8

Channel 2 or 6

Display POTs for

Channel 2 or 6

see Caution

Display POTs for

Channel 3 or 7

see Caution

Display POTs for

Channel 4 or 8

see Caution

Fuse

Fuse

Fuse

Channel 1 or 5

1

2

3

4

5

9

6

8

7

Channel Terminal

Numbers used as
reference in Table 3

Channel Terminal

Typical Labeling

Channel Alarm Relays Jumper Positions

Jumper position on pins 1 & 2

for NC contact (factory setting)

Jumper position on pins 2 & 3

for NO contact