4.3 Operating Modes

4.3.1 Buzzer:

During normal operation, whenever there is a fault or an alarm, the buzzer is triggered. The buzzer is stopped by
pressing the

CLEAR

button or by clearing remotely. The buzzer emits a continuous sound when an alarm threshold is

exceeded.

4.3.2 Light-emitting Diodes (LED)

Each channel has 5 LEDs that are visible and labeled on the FRONT panel. See Figure 4.

Table 5: Front Panel LED Indications

LED

Not Lighted

Lighted

Flashing

Green

Channel not in service

Channel in service

Upper Red

AL1 not triggered

AL1 threshold exceeded, with
automatic cancellation

AL1 threshold exceeded, with manual
cancellation, and not cleared

Center Red

AL2 not triggered

AL2 threshold exceeded, with
automatic cancellation

AL2 threshold exceeded, with manual
cancellation, and not cleared

Lower Red

AL3 not triggered

AL3 threshold exceeded on average
or lag, with automatic cancellation

Yellow

No fault

Channel faulty

Channel being calibrated or
programmed

4-20mA open (disconnected)

Figure 4: MX48 C

ONTROL

Front Panel

Previous

Next

Clear

Enter

Figure 4a: Front Panel Keypad Buttons

N

OTE

:

In some applications, slight electronic noise between the Sensor/Transmitter and the Control can cause

fluctuations in the display reading. These minor fluctuations are considered to be insignificant in terms of the
range, detection limit and alarm values of the gas being monitored.