5 domestic hot water – Glow-worm Ultrapower sxi User Manual

Page 16

Advertising
background image

16

5 Domestic Hot Water

5.6 SYSTEM REQUIREMENTS – Domestic Hot

Water

Domestic Hot Water Requirements

General - All domestic hot water circuits, connections, fittings

must be in accordance with the relevant standards and water

supply regulations.

For GB: Guidance G17 to G24 and recommendation R17 to

R24 of the Water Regulations Guide

(for Scotland, the Water

Byelaws 2000, Scotland)

.

Document G Sanitation, hot water safety and water efficiency,

section 3 of the building regulations, requires that the

installation of an unvented system should be notified to the

local authority Building Controls Department and that the work

must be carried out by a competent person approved at the

time by the Health and Safety Executive, as defined in the

approved document G3.

For IE: The current edition of I.S.813 “Domestic Gas

Installations”.

Where a storage system will not have a vent to atmosphere

the installation must comply with the building regulations and

the Water Supply (water fittings) regulations 1999 and water

byelaws 2000, Scotland, see also the current issue of BS5546

and BS6700.

If fitting to an existing system the local authority should be

informed.

NOTE:

Bye-laws of the appropriate Water Undertake also apply.

Discharge Pipework

It is a requirement of Building Regulation G3 that any

discharge from an unvented system is conveyed to where it

is visible but will not cause danger to persons in or about the

building. The tundish and discharge pipes should be fitted in

accordance with requirements and guidance notes of Building

Regulation G3.

NOTE: The tundishes are factory fitted during manufacture.

The discharge pipe (D2) from the tundish should terminate in

a safe place where there is no risk to persons in the vicinity of

the discharge, preferably be of metal and:

a) Be at least one pipe size larger than the nominal outlet

size of the safety device unless its total equivalent hydraulic

resistance exceeds that of straight pipe 9m long i.e. discharge

pipes between 9m and 18m equivalent resistance length

should be at least two sizes larger than the nominal outlet

size of the safety device, between 18 and 27m at least 3

sizes larger and so on. Bends must be taken into account in

calculating the flow resistance.

An alternative approach for sizing discharger pipes would be

to follow BS67100:1987 specification for design installation,

testing and maintenance of services supplying water for

domestic use within buildings and their curtilages. Appendix E

section E2 and table 21.

b) Have a vertical section of at least 300mm long, below the

tundish before any elbows or bends in the pipework.

c) Be installed with a continuous fall.

d) Have discharges visible at both the tundish and the

final point of discharge but where this is not possible or is

practically difficult there should be clear visibility at one or

other of these locations. Examples of acceptable discharge

arrangements are:

i) Ideally below a fixed grating and above the water seal in a

trapped gully.

ii) Downward discharges at low level; i.e. up to 100mm above

external surfaces such as car parks, hard standings, grassed

areas etc. are acceptable providing that where children may

play or otherwise come into contact with discharges a wire

cage or similar guard is positioned to prevent contact whilst

maintaining visibility.

iiI) Discharges at high level; e.g. into a metal hopper and

metal down pipe with the end of the discharge pipe clearly

visible (tundish visible or not) or onto a roof capable of

withstanding high temperature discharges of water and 3m

from any plastic guttering system that would collect such

discharges (tundish visible).

iv) Where a single pipe serves a number of discharges,

such as in blocks of flats, the number served should be

limited to not more than 6 systems so that any installation

discharging can be traced reasonably easily. The single

common discharge pipe should be at least one pipe size

larger than the largest individual discharge pipe (D2) to

be connected. If unvented hot water storage systems are

installed where discharges from safety devices may not be

apparent i.e. in dwellings occupied by blind, infirm or disabled

people, consideration should be given to the installation of an

electronically operated device to warn when discharge takes

place.

Advertising