LINK Systems OmniLink 5000 User Manual

Page 90

Advertising
background image

6.20

17 (OR-1)

2

Delayed Main Motor

6.3.1

18 (OR-2)

2

Hydraulic Overload Cylinder

6.1.12

19 (OR-3)

2

Hydraulic Overload Pump

6.1.12

20 (OR-4)

2

Flywheel Brake

6.3.2

21 (OR-5)

2

Lube System Output

6.1.11

22 (OR-6)

2

Auxiliary Equipment Stop

6.3.3

23 (OR-7)

2

Auxiliary Equipment Stop

6.3.3

24 (OR-8)

2

Slide Motion

6.3.4

25 (OR-9)

4

Press in Inch/Timed Inch

6.3.5

26 (OR-10)

4

Press in Manual Stroke Modes

6.3.5

27 (OR-11)

4

Press in Continuous Mode

6.3.5

28 (OR-12)

4

Press in Auto Single Stroke

6.3.5

29 (OR-13)

4

Aux. Lube 1 Output

6.2.1

30 (OR-14)

4

Aux. Lube 2 Output

6.2.1

31 (OR-15)

4

Stroking Enabled

6.3.6

32 (OR-16)

4

Stop At Top Output

6.3.7

Section 6.3.1 Delayed Main Motor

This output (OR-1) tracks the state of the main motor. If the main motor turns ON, this output will delay
a specified time before turning ON. When the main motor turns OFF, this output will delay a specified
time before turning OFF. The time for turn ON and turn OFF can be individually programmed by the
factory within the range of 0 seconds to 120 seconds.

Section 6.3.2 Flywheel Brake

This output (OR-4) turns on (flywheel brake is released) any time the forward or reverse motor input turns
ON (+24v). It turns OFF when both motor inputs turn OFF unless the press mode is in Inch or Timed
Inch. This feature allows the press to be "dead motor inched".

Section 6.3.3 Auxiliary Equipment Stop

Output (OR-6) provides a stop signal to equipment external to the press control. A stop signal is issued
(Output is turned Off) if the emergency stop button is pressed, auxiliary cycle stop input opens, die block
input opens, auxiliary master stop input opens, master stop switch opens, or the main motor is in reverse.
If the optional third input card exists, a stop signal is issued if any cycle stop input, except Input # 68, or
master stop input opens, or if either run mode interlock opens while in a stroking mode other than Inch
or Timed Inch. A stop signal is issued if the light curtain causes the press to stop (i.e. is not being muted),
except in the Inch mode. If configured to mute in Inch, the light curtain will not issue an auxiliary stop.
This is done so that the light curtain can be blocked while setting up the feed in Inch. If configured to
never mute the light curtain (type 004), this output turns off anytime light curtain is blocked.
Output (OR-7) turns Off if either the Tonnage Monitor or the Die Protection Module generates a cycle
stop or a top stop. If a top stop is generated this output will turn Off as soon as the condition occurs
while the press may continue to run to the top of the stroke.