Figure-7. Bypass Damper Wiring Schematic



Operation Checklist

• Verify that proper safety precautions have been followed.

• Electrical power must be locked off.

Check fan mechanism components:

• Nuts, bolts, set screws are tight.

• Mounting connections are properly made and tightened.

• Bearings are properly lubricated.

• Wheel, drives and fan surfaces are clean and tightened.

• Rotating assembly turns freely and does not rub.

• Drives on correct shafts, properly aligned, and properly tensioned.

Check fan electrical components:

• Motor is wired for proper supply voltage.

• Motor was properly sized for power of rotating assembly.

• Motor is properly grounded.

• All leads are properly insulated.

Trial “bump”:

• Turn on power just long enough to start assembly rotating.

• Check rotation for agreement with rotation arrow.

• Listen for any unusual noise.

Run unit up to speed:

• Bearing temperatures are acceptable (<200°F) after one to two hours of operation.

• Check for excess levels of vibration. Filter in readings should be 0.15 inches per second or less.

After one week of operation:

• Check all nuts, bolts and setscrews and tighten if necessary.

• Readjust drive tension if necessary.