Roof Curb Attachment

1. Lift the fan onto the roof curb. Make sure the fan securely

sits on the curb and level.

2. It is recommended to secure the fan in place on the curb

with lag bolts spaced at minimum 6” centers.

3. Pre-drill pilot holes through the side of the fan curb cap

and into the curb wood nailer strip.

4. To prevent any possible water penetration, fill the entire

pilot hole or bolt thread with exterior grade, waterproof

silicone caulking.

5. Secure into place through the pilot holes with stainless

steel, lag bolts. Some caulking will be forced out of the

hole to form a better barrier around the fixing.

Vibration Isolators

To prevent vibration and noise from being transferred to

the building, vibration isolators are recommended. Isolators

should be located between the fan system and the support

structure. M.K. Plastics supplies three main types of isolators

for FRP fans:

Floor Mounted Spring Isolators (floor mounting)

Floor Mounted Rubber-In-Shear Isolators (floor

mounting)

Hanging Spring Isolators (ceiling mounting)

Refer to the M.K. Plastics submittal for isolator installation

and adjustment instructions. In applications where seismic

isolators are required, contact M.K. Plastics directly for

further details.

M.K. Plastics Corp. Montréal, Québec www.mkplastics.com

Page. 2

Exhaust & Supply Roof Installation

AXTC fans that are roof mounted with curbs should be

securely attached to roof structure such as structural steel,

concrete or wooden decks. Roof structure supports per

structural engineer, in accordance with load requirements

and applicable building codes.

Concrete Roof Deck

Structural Steel Support

Wood Roof Deck

Roof Curb

Structural Steel Support

Continuous/Stitch Weld

Roof Curb

Roof Curb

Concrete Structure

Ø

1

2

" Anchor Bolts at 6" centers,

(4" max' spacing from curb corner)

Wooden Structure

Ø

1

2

" Lag Bolts at 6" centers,

(to be determined by structural engineer)

Roof Curb

Structural Steel Support

Continuous/Stitch Weld

Roof Curb

Roof Curb

Concrete Structure

Ø

1

2

" Anchor Bolts at 6" centers,

(4" max' spacing from curb corner)

Wooden Structure

Ø

1

2

" Lag Bolts at 6" centers,

(to be determined by structural engineer)

Roof Curb

Structural Steel Support

Continuous/Stitch Weld

Roof Curb

Roof Curb

Concrete Structure

Ø

1

2

" Anchor Bolts at 6" centers,

(4" max' spacing from curb corner)

Wooden Structure

Ø

1

2

" Lag Bolts at 6" centers,

(to be determined by structural engineer)

Lag Bolts

Roof Curb

Curb Cap

Figure 2.

Roof Mounted AXTC Fan

Spring Isolator

Rubber-In-Shear

Isolator

Hanging Spring

Isolator

Figure 3.

Vibration Isolators (Typical)