List of parameter, List of setup setting displays, Changing the user level – Nor-Cal SDC15 Controller User Manual

Page 4: Mode sp ev pi d para et stup, Evcf di do uf loc i d changing the user level

Advertising
background image

6

[Mode bank]

List of parameter

List of operation displays

List of parameter setting displays

Display

Item

Contents

Initial value Setting value

A--M

AUTO/MANUAL

AUTO: AUTO mode MAN: MANUAL mode

AUTO

r--r

RUN/READY

RUN: RUN mode RDY: READY mode

RUN

At

AT stop/start

At. OF: AT stop At. ON: AT start

AT stop

do Lt

Release all DO latches

Lt. ON: Latch continue Lt. OF: Latch release Latch continue

C. dI 1

Communication DI1

dI . OF: OFF dI . On: ON

OFF

*1 0: Unit of "1s" 1: Fixed at 0.5s 2: Fixed at 0.2s 3: Fixed at 0.1s
*2 5 to 120s when output includes the relay output

: Essential parameters for PV measurement and control
: Basic parameters
: Required parameters when using optional functions

[Extended tuning bank]

*1 Normal = Standard control characteristics, Immediate response = Control characteristics that respond immedi-

ately to external disturbance, Stable = Control characteristics having less up/down fluctuation of PV

[Setup bank]

List of setup setting displays

Display

Item

Contents

Initial value

Setting value

At.ty

AT type

0: Normal 1: Immediate response 2: Stable *1

1

JF.bd

● Just-FiTTER setting band

0.00 to 10.00

0.30

SP.LG

● SP lag constant

0.0 to 999.9

0.0

At-P

● Proportional band tuning factor at AT 0.00 to 99.99

1.00

At-I

● Integral time adjust at AT

0.00 to 99.99

1.00

At-d

● AT Derivative time adjust

0.00 to 99.99

1.00

Ctr.A

Control algorithm

0: PID(Conventional PID)

0

1: Ra-PID(High-performance PID)

JF.Ov

Just-FiTTER oversheet suppression factor 0 to 100

0

St.SA

● ST step execution resolution band 0.0 to 99.99

10.0

St.Sb

● ST step setting band

0.0 to 10.00

0.50

St.Hb

● ST hunting setting band

0.0 to 10.00

1.00

St.ud

● ST step ramp change

0: ST is executed when the PV moves up or down.

0

1: ST is executed only when the PV moves up.

Display

Item

Contents

Initial value Setting value

Upper display: PV
Lower display: SP

PV

SP(Target value)

SP low limit to SP high limit

0

SP
LSP 1 (Display example) LSP group number

1 to LSP system group (Max. 4)

1

LSP

(1st digit=the right end digit)

PV

MV (Manipulated Variable) -10.0 to +110.0%

MV

Setting is enabled in MANUAL mode
(Numeric value flashed)

HEAt

Heat MV (Manipulated Variable) Setting is disabled.

Numeric value

-10.0 to +110.0%

COOL

Cool MV (Manipulated Variable)

Numeric value
PV

AT progress display

Setting is disabled.

At 1 (Display example)

(1st digit=the right end digit)

Ct 1

CT current value 1

Setting is disabled.

Numeric value
Ct2

CT current value 2

Setting is disabled.

Numeric value
E 1

Internal Event 1 main setting

-1999 to +9999U or 0 to 9999U

0

Numeric value
E 1. Sb

Internal Event 1 sub setting

Numeric value
t 1. --(Display example) Internal Event 1 remaining Setting is disabled.

Numeric value

time

"

", is displayed at the right end digit when using

the ON delay time, and "L" , the OFF delay time.

E2

Internal Event 2 main setting

Same as Internal Event 1 main setting

0

Numeric value
E2. Sb

Internal Event 2 sub setting Same as Internal Event 1 sub setting

0

Numeric value
t2. --(Display example) Internal Event 2 remaining Same as Internal Event 1 remaining time

Numeric value

time

E3

Internal Event 3 main setting

Same as Internal Event 1 main setting

0

Numeric value
E3. Sb

Internal Event 3 sub setting Same as Internal Event 1 sub setting

0

Numeric value
t3. --(Display example) Internal Event 3 remaining Same as Internal Event 1 remaining time

Numeric value

time

L

[SP bank]

[Event bank]

[PID bank]

[Parameter bank]

Display

Item

Contents

Initial value

Setting value

CtrL

Control method

0: ON/OFF control 1: Fixed PID

0 or 1

2: ST(Self-tuning)

At. OL

MV low limit at AT

-10.0 to +110.0%

0.0

At. OH

MV high limit at AT

-10.0 to +110.0%

100.0

dI FF

Differential (for ON/OFF control) 0 to 9999U

5

OFFS

● ON/OFF control action point offset -1999 to +9999U

0

FL

PV filter

0.0 to 120.0s

0.0

rA

● PV ratio

0.001 to 9.999

1.000

bI

PV bias

-1999 to +9999U

0

CyU

● Time proportional cycle unit 1 0 to 3

*1

0

Cy

Time proportional cycle 1

5 to 120s or 1 to 120s

*2

10 or 2

CyU2

● Time proportional cycle unit 2 0 to 3

*1

0

Cy2

Time proportional cycle 2

5 to 120s or 1 to 120s

*2

10 or 2

tP.ty

● Time proportional cycle mode 0: Controllability aiming type

0 or 1

1: Operation end service life aiming type(Only ON/

OFF operation within Time proportional cycle)

SPU

● SP up ramp

0.0 to 999.9U(No ramp when set at "0.0U")

0.0

SPd

● SP down ramp

0.0

Display

Item

Contents

Initial value

Setting value

SP- 1 to SP-4 SP of LSP 1 group to 4 group

SP low limit to SP high limit

0

U: Unit Maximum unit of Industrial vol-

ume in PV range (°C, Pa,L/min, etc.)

MOdE

SP

Ev

PI D

PARA

Et

StUP

Display

Item

Contents

Initial value

Setting value

E 1 to E5

Internal Event 1 to 5 main setting -1999 to +9999 or 0 to 9999

0

E 1.Sb to E5.Sb

Internal Event 1 to 5 sub setting (The decimal point position may vary so that it

meets the operation type of the internal event)

E 1.Hy to E5.Hy

Internal Event 1 to 5 hysteresis

0 to 9999

5

(The decimal point position may vary so that it
meets the operation type of the internal event)

E 1.On to E5.On

● Internal Event 1 to 5 ON delay time 0.0 to 999.9 or 0 to 9999

0

E 1.Of to E5.Of

● Internal Event 1 to 5 OFF delay time

[DO assignment bank]

Display

Item

Contents

Initial value Setting value

Ot 1. 1 to Ot2. 1

● Operation type (Control output 1 to 2, 0: Default output 1 to 2: MV1 to 2

0

Ev 1. 1 to Ev3. 1

Event output 1 to 3)

3 to 6: Function 1 to 4

Ot 1.2 to Ot2.2

● Output assign A (Control output 1 to 2, 0: Normally opened 1: Normally closed

14: Output 1

Ev 1.2 to Ev3.2

Event output 1 to 3)

2 to 6: Internal Event 1 to 5

15: Output 2

7 to 13: Undefined 14 to 15: MV1 to 2

2: Event 1

16 to 17: Undefined 18 to 19: DI1 to 2

3: Event 2

20 to 25: Undefined

4: Event 3

Ot 1.3 to Ot2.3

● Output assign B (Control output 1 to 2, 26 to 28: Internal Contact 1 to 3

0

Ev 1.3 to Ev3.3

Event output 1 to 3)

29 to 33: Undefined 34 to 37: DI1 to 4
38: MANUAL 39: READY 40: Undefined

Ot 1.4 to Ot2.4

● Output assign C (Control output 1 to 2, 41: AT running 42: During SP ramp 43: Undefined

0

Ev 1.4 to Ev3.4

Event output 1 to 3)

44: Alarm occurs 45: PV alarm occurs
46: Undefined 47: Mode key pressing status

Ot 1.5 to Ot2.5

● Output assign D (Control output 1 to 2, 48: Event output 1 status

0

Ev 1.5 to Ev3.5

Event output 1 to 3)

49: Control output 1 status

Ot 1.6 to Ot2.6

● Control output 1 to 2, Event output

The digits are determined to 1st, 2nd, 3rd,

Ev 1.6 to Ev3.6

1to 3 Polarity A to D

and 4 th digit from the right end.

1st digit: Polarity A

0: Direct 1: Reverse

0

2nd digit: Polarity B

0

3rd digit: Polarity C

0

4the digit: Polarity D

0

Ot 1.7 to Ot2.7

● Polarity (Control output 1 to 2, 0: Direct 1: Reverse

0

Ev 1.7 to Ev3.7

Event output 1 to 3)

Ot 1.8 to Ot2.8

● Latch (Control output 1 to 2, 0: None 1: Latch (Latch at ON)

0

Ev 1.8 to Ev3.8

Event output 1 to 3)

2: Latch (Latch at OFF except for initialization

at power ON)

[User function bank]

Display

Item

Contents

Initial value Setting value

UF- 1 to UF-8

● User function 1 to 8

[Lock bank]

Display

Item

Contents

Initial value Setting value

LOC

Key lock

0: All settings are possible

0

1: Mode, event, operation display, SP, UF, lock,

manual MV, [mode] key can be set

2: Operation display, SP, UF, lock,

manual MV, [mode] key can be set

3: UF, lock, manual MV, [mode] key can be set

C.LOC

● Communication lock

0: read/write enabled 1: read/write disabled

0

L.LOC

● Loader lock

0: read/write enabled 1: read/write disabled

0

PASS

Password display

0 to 15(5: Password 1A to 2B display)

0

PS 1A

Password 1A

0000 to FFFF (Hexadecimal value)

0000

PS2A

Password 2A

0000 to FFFF (Hexadecimal value)

0000

PS 1b

Password 1B

0000 to FFFF (Hexadecimal value)

0000

PS2b

Password 2B

0000 to FFFF (Hexadecimal value)

0000

[Instrument information bank]

Display

Item

Contents

Initial value Setting value

I d0 1

● ROM ID

0: SDC15

0

I d02

● ROM Version 1

XX. XX (2 digits after decimal point)

I d03

● ROM Version 2

XX. XX (2 digits after decimal point)

I d04

● Loader information

I d05

● EST information

I d06

● Manufacturing date code

Subtract 2000 from the year.

(year)

Example: "3" means the year 2003.

I d07

● Manufacturing date code

Month + day divided by 100.

(month, day)

Example: "12.01" means the 1st day of December.

I d08

● Serial No.

[Event configuration bank]

[DI assignment bank]

Precaution for setup

· The type of auto tuning can be changed by changing the value of At.ty (AT

type) in the extended tuning bank. Set it to match the control characteristics.

If necessary press
[mode] once to
change to the
operation display.
Next, press and
hold [para] for
more than 2s to
get the parameter
setup display.

a--M

or

r--r

appears

on the upper display.

Press and hold
[para] for more
than 2s again to
display

c 01

on the

upper display.

Press [para]
repeatedly to
change the upper
display to

c 79

(user level).

When [<], [ ] or
[ ] is pressed, the
lower display
flashes and can be
changed to the
desired numerical
value. Then, if no
key is pressed for
more than 2s, the
displayed value is
set and the display
changes from
flashing to continu-
ously lit.

<

<

0: Simple configuration
(initial value)
1: Standard configuration
2: High function configu-
ration

Changing the user level

Display

Item

Contents

Initial value Setting value

di 1. 1 to dI 3. 1

Internal contact 1 to 3

0: No function 1: LSP group selection (0/+1)

0

Operation type

2: LSP group selection (0/+2)
3: LSP group selection (0/+4) 4: Invalid
5: Invalid 6: Invalid 7: RUN/READY selection
8: AUTO/MANUAL selection
9: LSP/RSP selection 10: AT Stop/Start
11: ST disabled/enabled
12: Control action direct/reverse
13: SP Ramp enabled/disabled
14: PV Hold 15: PV Maximum value hold
16: PV Minimum value hold 17: Timer Stop/Start
18: Release all DO latches (Continue/Release)
19: Invalid 20: Invalid

dI 1.2 to dI 3.2

● Internal contact 1 to 3

0: Not used (Default input)

0

Input bit function

1: Function 1 ((A and B) or (C and D))
2: Function 2 ((A or B) and (C or D))
3: Function 3 (A or B or C or D)
4: Function 4 (A and B and C and D)

dI 1.3 to dI 3.3

● Internal contact 1 to 3

0: Normally opened 1: Normally closed

2: Contact 1

Input assign A

2: DI1 3: DI2 4 to 9: Undefined

3: Contact 2

10 to 14: Internal Event 1to 5

4: Contact 3

dI 1.4 to dI 3.4

● Internal contact 1 to 3

15 to 17: Undefined

0

Input assign B

18 to 21: Communication DI1 to 4

dI 1.5 to dI 3.5

● Internal contact 1 to 3

22: MANUAL 23: READY 24: Undefined

0

Input assign C

25: AT running 26: During SP ramp 27: Undefined

dI 1.6 to dI 3.6

● Internal contact 1 to 3

28: Alarm occurs 29: PV alarm occurs

0

Input assign D

30: Undefined 31: mode key pressing status
32: Event output 1 status 33: Control output 1 status

dI 1.7 to dI 3.7

● Internal contact 1 to 3

The digits are determined to 1st, 2nd, 3rd

Polarity A to D

and 4th digit from the right end.

1st digit: Polarity A

0: Direct 1: Reverse

0

2nd digit: Polarity B

0

3rd digit: Polarity C

0

4th digit: Polarity D

0

dI 1.5 to dI 3.5

● Internal contact 1 to 3 Polarity

0: Direct 1: Reverse

0

dI 1.9 to dI 3.9

● Internal contact 1 to 3

0: Every Internal Event

0

Event channel def.

1 to 5: Internal Event No.

Memo

• Items marked

● in the tables are displayed in standard and/or high function configuration.

• To change a user level, refer to

in the lower right part of this page.

This controller's user level can be set to 1 of 3 types in setup
C79.
The number of possible displays and settings decreases
according to the user level: high function > standard > sim-
ple. All items are displayed when high function is selected.

EvCF

di

dO

UF

LOC

I d

Changing the user level

Display

Item

Contents

Initial value

Setting value

P- 1

Proportional band (PID1)

0.1 to 999.9%

5.0

I - 1

Integral time (PID1)

0 to 9999s (No integration control action when set at "0")

120

d- 1

Derivative time (PID1)

0 to 9999s (No derivative control action when set at "0")

30

rE- 1

Manual reset (PID1)

-10.0 to +110.0%

50.0

OL- 1

● MV low limit (PID1)

-10.0 to +110.0%

0.0

OH- 1

● MV high limit (PID1)

-10.0 to +110.0%

100.0

P- 1C

Proportional band (cool) (PID1) 0.1 to 999.9%

5.0

I - 1C

Integral time (cool) (PID1)

0 to 9999s (No integration control action when set at "0")

120

d- 1C

Derivative time (cool) (PID1)

0 to 9999s (No derivative control action when set at "0")

30

OL. 1C

● Output low limit (cool) (PID1) -10.0 to +110.0%

0.0

OH. 1C

● Output high limit (cool) (PID1) -10.0 to +110.0%

100.0

Display

Item

Contents

Initial value

Setting value

C0 1

PV input range type

For details, refer to the PV Input Range Table Depending on Model No.

C02

Temperature unit

0: Celsius (°C) 1: Fahrenheit (°F)

0

C03

● Cold junction compensation

0: Performed (internal) 1: Not performed (external)

0

C04

Decimal point position

0: No decimal point 1 to 3: 1 to 3 digits below decimal point

0

C05

PV input range low limit

When the PV input type is DC voltage/DC current,

0

C06

PV input range high limit

-1999 to +9999U

1000

C07

● SP low limit

PV input range low limit to PV input range

C08

● SP high limit

high limit

C09

● PV square root extraction dropout 0.0 to 100.0% (PV square root extraction

0.0

is not performed when set at "0.0".)

C 14

Control action (Direct/Reverse)

0: Heat control (Reverse action)

0

1: Cool control (Direct action)

C 15

● Output operation at PV alarm 0: Control calculation is continued.

0

1: Output at PV alarm is output.

C 16

● Output at PV alarm

-10.0 to +110.0%

0.0

C 17

● Output at READY (Heat)

-10.0 to +110.0%

0.0

C 18

● Output at READY (Cool)

-10.0 to +110.0%

0.0

C 19

● Output operation at changing AUTO/MANUAL

0: Bumpless transfer 1: Preset

0

C20

● Preset MANUAL value

-10.0 to +110.0%

0.0 or 50.0

C2 1

● Initial output type of PID control

0: Auto 1: Not initialized 2: Initialized

0

C22

● Initial output of PID control

-10.0 to +110.0%

0.0 or 50.0

C26

Heat/Cool control

0: Not used 1: Used

0

C27

● Heat/Cool selection

0: Normal 1: Energy saving

0

C28

Heat/Cool control dead zone -100.0 to +100.0%

0.0

C29

● Heat/Cool control change point -10.0 to +110.0%

50.0

C30

LSP system group

1 to 4

1

C32

● SP ramp unit

0: 0.1U/s 1: 0.1U/min 2: 0.1U/h

1

C36

CT1 operation type

0: Heater burnout detection 1: Current value measurement

0

C37

CT1 output

0 to 1: Control output 1 to 2, 2 to 4: Event output 1 to 3

0

C38

CT1 measurement wait time

30 to 300ms

30

C39

CT2 operation type

Same as CT1

0

C40

CT2 output

Same as CT1

0

C4 1

CT2 measurement wait time

Same as CT1

30

C42

Control output 1 range

1: 4 to 20mA 2: 0 to 20mA

1

C43

Control output 1 type

0: MV 1: Heat MV 2: Cool MV 3: PV

0

4: PV before ratio, bias, and filter
5: SP 6: Deviation 7: CT1 current value
8: CT2 current value 10: SP+MV 11: PV+MV

C44

Control output 1 scaling low limit -1999 to +9999U

0.0

C45

Control output 1 scaling high limit

100.0

C46

Control output 1 MV scaling

0 to 9999 (Valid when control output 1 type is 10 or 11)

200

C47

Control output 2 range

Same as control output 1

1

C48

Control output 2 type

Same as control output 1

3

C49

Control output 2 scaling low limit Same as control output 1

0

C50

Control output 2 scaling high limit Same as control output 1

1000

C5 1

Control output 2 MV scaling

Same as control output 1

200

C64

CPL/MODBUS

0: CPL 1: MODBUS (ASCII format)

0

2: MODBUS (RTU format)

C65

Station address

0 to 127 (Communication is disabled when set at "0".)

0

C66

Transmission speed (bps)

0: 4800 1: 9600 2: 19200 3: 38400

2

C67

Data format (Data length)

0: 7 bits 1: 8 bits

1

C68

Data format (Parity)

0: Even parity 1: Odd parity 2: No parity

0

C69

Data format (Stop bit)

0: 1 bit 1: 2 bits

0

C70

● Response time-out

1 to 250ms

3

C7 1

● Key operation type

0: Standard type 1: Special type

0

C72

[mode] key function

0: Invalid 1: AUTO/MANUAL selection

0

2: RUN/READY selection 3: AT Stop/Start
4: LSP group selection 5: Release all DO latches
6: Invalid 7: Communication DI1 selection 8: Invalid

C73

● MODE display setup

Bit 0: AUTO/MANUAL display (Enabled: +1)

255

(Sum of the weighting)

Bit 1: RUN/READY display (Enabled: +2)
Bit 3: AT Stop/Start display (Enabled: +8)
Bit 4: Release all DO latches display (Enabled: +16)
Bit 5: Communication DI1 ON/OFF display (Enabled: +32)
Other invalid setting, 0, +4, +64, +128

C74

● PV/SP display setup

Bit 0: PV display (Enabled: +1)

15

(Sum of the weighting)

Bit 1: SP display (Enabled: +2)
Bit 2: LSP group number display (Enabled: +4)
Other invalid setting, 0, +8

C75

● MV display setup

Bit 0: MV display (Enabled: +1)

15

(Sum of the weighting)

Bit 1: Heat MV/cool MV display (Enabled: +2)
Bit 3: AT progress display (Enabled: +8)
Other invalid setting: 0, +4

C76

● EV display setup

0: Not displayed

0

(Operation display)

1: Set value of Internal event 1 is displayed
2: Set values of Internal event 1 to 2 are displayed
3: Set values of Internal event 1 to 3 are displayed

C77

● Timer remain time display setup

0: Not displayed

0

(Operation display)

1: Internal event 1 is displayed
2: Internal event 1 to 2 is displayed
3: Internal event 1 to 3 is displayed

C78

● CT display setup

0: Not displayed 1: CT1 current value is displayed

1

(Operation display)

2: CT1 to 2 current values are displayed

C79

User level

0: Simple configuration 1: Standard configuration

0

2: High function configuration

C80

● Communication monitor

0: Not used

0

display

1: Flashing while data is sending through

RS-485 communication.

2: Flashing while data is receiving through

RS-485 communication

3: Logical OR of all DI statuses
4: Flashing in READY mode

C90

● Number of CT1 turns

0: 800 turns 1 to 40: CT turns divided by 100

8

C9 1

● Number of CT1 power wire loops

0: 1 time 1 to 6: Number of times

1

C92

● Number of CT2 turns

0: 800 turns 1 to 40: CT turns divided by 100

8

C93

● Number of CT2 power wire loops

0: 1 time 1 to 6: Number of times

1

7

Analog input

Control action

SP

Continuous output

Communication

Key operation • display

Control

PV

Time proportional output

SP

Display

Item

Contents

Initial value Setting value

E 1.C 1 to E5.C 1

Internal event 1 to 5 Configuration 1 Refer to event type (see page 8)

0

Operation type

E 1.C2 to E5.C2

Internal event 1 to 5 Configuration 2 The digits are determined to 1st, 2nd, 3rd,
Operation type

and 4th digit from the right end.

1st digit: Direct/Reverse

0: Direct 1: Reverse

0

2nd digit: Standby

0: None 1: Standby 2: Standby + Standby at SP change

0

3rd digit: EVENT state at READY

0: Continue 1: Forced OFF

0

4th digit: Undefined

0

0

E 1.C3 to E5.C3

● Internal event 1 to 5 Configuration 3 The digits are determined to 1st, 2nd, 3rd,

and 4th digit from the right end.

1st digit: Controller alarm OR

0: None 1: Alarm direct + OR operation

0

2: Alarm direct + AND operation
3: Alarm reverse + OR operation
4: Alarm reverse + AND operation

2nd digit: Special OFF setup

0: As usual

0

1: When the event set value (main setting)
is 0, the event is "OFF".

3rd digit: Delay unit

0: 0.1s 1: 1s 2: 1min

0

4th digit: Undefined

0

0