REFCO DIGIMON User Manual

Page 4

Advertising
background image

HVAC/R

Service Products

Setting Temperature units

Hold the ENTER button and press the R- button to select the desired tempera-

ture unit °F/ °C.

Note: Selected settings will be stored in memory until the next manual change

is made.

Back Light

Press the LIGHT button and the back light will switch on for approximately 30

seconds.

Auto Shut-Off

Approximately 10 minutes after the last measurement or key press the

DIGIMON shuts off itself.

SUPERHEAT/SUBCOOL

Chosen refrigerant and the measured temperature of the external K-type ther-

mocouple (6) or the clamp thermocouple K- type (7).

Changing Superheat/Subcool

Hold the ENTER button and press the

SUPERHEAT/SUBCOOL

to switch bet-

ween superheat and subcool.

Vacuum mode

Press the VAC button to display vacuum mode. Press the VAC button again to

quit this function.

Reading the Vacuum display:

The level of vacuum is shown on the display with (5) five vacuum bars. During

evacuation, the vacuum bars will increase from (1) one bar, no vacuum, to a

maximum of (5) five bars, high vacuum. The more bars displayed, the higher

the vacuum. For a more detailed vacuum level see vacuum specifications.

Note: The DIGIMON must be powered ON before connecting the hoses and

switching on the vacuum pump. If this is not in the correct order the vacuum

display will not show the correct vacuum level.

Note: The DIGIMON must stay powered ON while pulling a vacuum. If the DI-

GIMON is powered OFF while pulling a vacuum, the vacuum display will not

show the correct vacuum level.

The end-vacuum depends on the capacity of the vacuum pump and the current

atmospheric pressure.
For an exact level of vacuum and for vacuum leak checking it is recommended

to use a separate micron vacuum gauge like the VG-64 or the Absolute-Vacuum

Gauge 19621(see REFCO catalog).

Reset

For best results it is recommended to reset/zero the manifold periodically every

40 to 50 hours.

1. Disconnect any hoses.

2. Open low side (blue) and high side (red) valves.

3. Turn on the manifold by pressing the ON / OFF button for 1 second.

4. Press and hold ENTER and LIGHT button at the same time.

5. When the word “ZEro” is shown on the display release ENTER and LIGHT

buttons.

VAC

VAC

LIGHT

ENTER

ENTER

R-

SUPERHEAT/SUBCOOL

REFCO Manufacturing Ltd.

Telefon +41 41 919 72 82

Industriestrasse 11

Telefax +41 41 919 72 83

CH-6285 Hitzkirch (Switzerland)

[email protected] www.refco.ch

ENTER

ENTER

LIGHT

LIGHT

ON / OFF

4