Sanuvox R+ User Manual

R+ installation manual, Warning, Please save for your records

Advertising
background image

Operation

1.

Once installed, the Sanuvox R+ should preferably be plugged into a conditioned dedicated 110V outlet. If one is not available, an

extension cord may be used. For 220V applications, the Sanuvox R+ plug may be cut and hardwired to a dedicated 220V source.

IMPORTANT: When the Sanuvox R+ is turned on, The <<STAND-BY>> icon will appear on the LCD display. The Sanuvox R+ must first go

through a warm-up not lasting more than 45 seconds, after which time the unit will become operational and the <<STAND-BY>> icon will

begin to blink. THE UNIT WILL NOT FUNCTION UNTIL THE WARM-UP IS COMPLETE.

2.

To turn the Sanuvox R+ 'ON', press the toggle switch on the center of the front cover to the 'ON' position. The <<STAND-BY>> icon will

appear on the LCD display not lasting more than 45 seconds (warm up). After the warm-up, the purifier will be in "Stand-By Mode" (<<Stand-

By>> will begin to blink). The purifier will remain in Stand-By Mode until the purifier senses air-flow.

3.

Upon sensing air-flow the purifier will automatically switch to "Air Purification Mode" The <<STAND-BY>> icon will disappear and be replaced

with useful user information.

R+

INSTALLATION

MANUAL

PLEASE SAVE FOR YOUR RECORDS

Serial Number#

Date Installed:

Installed By:

Installers Contact info.:

SANUVOX TECHNOLOGIES INC. © 2011

Follow all safety codes.

Wear safety glasses and work gloves.

1-888-SANUVOX www.sanuvox.com

Before installing or performing maintenance or

service on the purifier, turn off main power switch

to unit. Electrical shock can cause injury or death.

There may be more than one disconnect switch.

Never expose eyes or skin to ultraviolet light from

any source. The Purifier MUST be DISCONNECTED
from power source before performing maintenance

or service. Personal injury may result.

Do not touch Lamp glass without gloves. Reduced

performance of Lamp may result. Clean Lamp after

handling.

Use only specified replacement Lamps with you

Purifier. Use of an incorrect Lamp can result in

damage to the Purifier and/or Lamp.

WARNING

WARNING

WARNING

The UV Lamp contains a small quantity of mercury.

If a Lamp breaks, clean and dispose of with care.

WARNING

WARNING

UNDERSTANDING THE LCD DISPLAY

Troubleshooting the UV Lamp
To check to make sure the UV Lamp has in fact failed:

UV LAMP RESET BUTTON (To be used to reset “Days Left” after UV Lamp change-out)

Disconnect the socket from the Lamp.

Placing the probe of the ohmmeter to one of the four pins on the end of the Lamp, touch the other probe of the ohmmeter to each of the other pins
until you find the matching pin. The ohmmeter will read approximately 3 ohms (almost a short). This indicates that the filament is good. Check the
other two pins. If both sets of filaments test OK, the Lamp is functioning. If one or both sets of filaments read an open circuit (infinity) on resistance,
the Lamp must be replaced.

To the right of the LCD screen is a small hole which houses the RESET BUTTON. To RESET the “Days Left” back to 1096, insert a small object
similar to a paper clip into the hole holding down the button for 3 seconds.

Solid for up to 45 seconds