Before installing or performing maintenance or service

on the purifier, DISCONNECT from main power.

Electrical shock can cause injury or death.

Never expose eyes or skin to ultraviolet light from any
source. The Purifier MUST be DISCONNECTED from

power source before performing maintenance or

service. Personal injury may result.

Do not touch Lamp glass without gloves. Reduced

performance of Lamp may result. Clean Lamp after

handling.

Use only specified replacement Lamps with your

Purifier. Use of an incorrect Lamp can result in damage

to the Purifier and/or Lamp.

WARNING

WARNING

WARNING

The UV Lamp contains a small quantity of mercury. If a

Lamp breaks, clean and dispose of with care.

WARNING

WARNING

SABER GENIUS

INSTALLATION

MANUAL

OPERATION

To start the purifier, press the 'ON' button. The LCD screen is illuminated
to show that power is on. Within a few seconds, the UV lamp will energize.

MAINTENANCE

Disconnect all power before performing any maintenance or service. The ultraviolet lamp should be cleaned every two to three months. To clean,
open the control box by loosening screws and pulling cover off. Next, disconnect white socket from lamp. Loosen the 3 screws on the retainer
ring. Turn retainer ring left. Pull out lamp (leave it in retainer ring). Wipe lamp with a soft tissue and alcohol based solution. Reverse the above
procedure to reinstall the lamp. Lamps need periodic replacement to maintain design specifications. Replace lamp after 1 year of operation.
Follow instructions below on how to Reset the Timer Feature. Contact a local dealer for replacement lamps

LAMP OPERATING STATUS

Troubleshooting the UV Lamp

Disconnect the white socket from the Lamp. Ohmmeter required.

Place one probe of the ohmmeter to one of the four pins on the end of the Lamp.
Touch the other probe of the ohmmeter to each of the other three pins until you
find the matching pin. The ohmmeter will read approximately 3 ohms (almost a
short). This indicates that the filament is good. Check the other two pins. If both
sets of filaments test OK, the Lamp is functioning. If one or both sets of filaments
read an open circuit (infinity) on resistance, the Lamp is defective.

The 'RESET Button' is used to:

1)

Reset an error code without losing 'DAYS LEFT'

Or

2)

Reset the unit back to original factory condition. This
includes resetting the 'Lamp Timer' feature back to 365 days.

Soft Reset

A 'Soft Reset' is used to clear an error-code message, or used after a
service call without resetting the lamp life timer.
To do a Soft Reset quickly press the reset button.

Hard Reset

A hard reset is used after a UV Lamp has been replaced with a new
Lamp. Using the Hard Reset will bring the unit back to Factory Condition
including resetting the Days Left to 365.
To do a Hard Reset press and hold the reset button for a minimum
of 3 seconds.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

SABER GENIUS

MANUAL

Follow all safety codes.

Wear safety glasses and work gloves.

PLEASE SAVE FOR YOUR RECORDS

Serial Number#

Date Installed:

Installed By:

Installers Contact info.:

SANUVOX TECHNOLOGIES INC. © 2010

1-888-SANUVOX www.sanuvox.com

24 / 110 VOLT UV SYSTEM

365

Days Left

Error-Code
EC1: Lamp failure
EC2: Ballast failure
EC3: 24V Power supply voltage too low**
EC4: 24V Power supply voltage too high**

365

Days Left

Days Left

EC2

A

B

C

E

D

G

G

F

A.

Day Counter - Provides lamp life remaining in days.

B.

UV Lamp Status - “UV Purifier Operating” will show unless:

Unit is OFF

Lamp has failed

Ballast has failed

Lamp is over 365 day life

C.

Change Lamp Indicator - After 325 days, CHANGE LAMP

will illuminate, indicating that lamp will need to be replaced

soon. After 365 days, CHANGE LAMP will flash indicating

it is time to replace lamp. CHANGE LAMP will also stay on

if the lamp fails before the 365 days is up.

D.

Timer - Rotating Circle indicates time counter. It will stop rotating

after 365 days.

E.

Day Counter - Bars will reduce in number each 45 days to

indicate lamp life left. At 365 days, no bars will be

displayed indicating the lamp should be replaced.

F.

CALL INSTALLER icon will illuminate under the following

conditions: 1) The Lamp has illuminated for 365 days and is in

need of replacement; 2) when an Error-Code (i.e. EC3) appears.

**In the event EC3 or EC4 appears, the 110/24V

step down transformer must be used.

EN

REV. 01 051210

REV. 01 051210