Typical Fixed Tank Installations
GENERAL NOTES:
1. 13mm (0.52”) mounting hole required on right-angle brackets.
2. Secure cable to bulkhead or tank wall using cable clips for 7mm - 8mm (0.28” - 0.32”)
dia. cable. Maximum distance between clips is 500mm (19.69”). Avoid strain on cable.
3. Use bulkhead seals suitable for 7mm - 8mm (0.28” - 0.32”) cable.
4. Terminate vent tube and connect cable within an environmentally protected enclosure.
15.0
MIN
0.59
DO NOT use
transmitter
as a step!
Support cable
on bulkhead
or cable tray.
Sludge Level Maximum
15.0
MIN
0.59
249.9
MIN
9.84
Sludge Level Maximum
Linear = mm/inches
Sludge Level Max.
300 MIN
11.81
35.0
MIN
1.38