Environmental Specifications

Environmental Tests

Industry Standards

Test Level Limits

Temperature (Operating)
(Performance Criteria A)

IEC60068-2-1: (Test Ad, Operating Cold),
IEC60068-2-2: (Test Bd, Operating Dry Heat),
IEC60068-2-14: (Test Nb, Operating Thermal
Shock)

0°C to +55°C

Temperature
(Non-operating)
(Performance Criteria B)

IEC60068-2-1:
(Test Ab, Unpackaged Non-operating Cold),
IEC60068-2-2:
(Test Bb, Unpackaged Non-operating Dry Heat),
IEC60068-2-14:
(Test Na, Unpackaged Non-operating Thermal
Shock)

-40°C to +85°C

Operating Altitude

2000 meters (6561 feet)

Not tested

Humidity (Operating)
(Performance Criteria A)

IEC60068-2-30:
(Test Db, Unpackaged Damp Heat):

5% to 95% non-condensing

Vibration (Operating)
(Performance Criteria A)

IEC60068-2-6: (Test Fc, Operating)

5G @ 10Hz to 500Hz, 0.030in.
max. peak-to-peak

Shock (Operating)
(Performance Criteria A)

IEC60068-2-27: (Test Ea, Unpackaged Shock)

30g,11ms half-sine (3 mutually
perpendicular axes)

Shock (Non-operating)
(Performance Criteria B)

IEC60068-2-27: (Test Ea, Unpackaged Shock)

50g, 11ms half-sine (3 mutually
perpendicular axes)

Radiated Emissions

CSIPR 11; Group 1, Class A
Rockwell Document QTP#X0327

(Enclosure) Class A, 30MHz to
1GHz

Conducted Emissions

IEC 61000-6-4:2007
Rockwell Document QTP#X0327

Group 1, Class A (AC Mains),
150kHz – 30MHz

ESD immunity
(Performance Criteria B)

IEC 61000-4-2
Rockwell Document QTP#X0327

6kV Indirect (Coupling Plate)
6kV Contact Discharge (to points
of initial contact)
8kV Air Discharge (to points of
initial contact)

Radiated RF immunity
(Performance Criteria A)

IEC 61000-4-3: Level 3
Rockwell Document QTP#X0327

10V/M with 1kHz sine-wave
80% AM from 80MHz to
2000MHz
10V/M with 200Hz sine-wave
50% Pulse 100% AM @900MHz
10V/M with 200Hz sine-wave
50% Pulse 100%AM
@1890MHz
1V/M with 1kHz sine-wave
80%AM from 2000MHz to
2700MHz
(3V/M goal)

EFT/B immunity
(Performance Criteria B)

IEC 61000-4-4*
Rockwell Document QTP#X0327

Signal Ports:
±3kV @ 5kHz for 5 minutes,
Criteria B
±2kV @ 5kHz for 5 minutes,
Criteria A
±2kV @ 5kHz for 5 minutes,
Criteria B (standard)

Power Ports:
±2kV @ 5kHz for 5 minutes,
Criteria A
±2kV @ 5kHz for 5 minutes,
Criteria B (standard)

Surge transient immunity
(Performance Criteria B)

IEC 61000-4-5
Rockwell Document QTP#X0327

Signal Ports:
±2kV line-earth {CM}@ 2Ω on
shielded ports

Power Ports
±2kV CM @ 12Ω
±1kV DM @ 2Ω