Defender Series Surge + PDU User Manual

© SurgeX

REV-C

Page 4

Plug in the Power Cord

o Connect the input power cord of the

SurgeX Defender Series to AC Mains.

Lock the

SX-DS-L630-FP and SX-DS-

L530-FP plugs

by turning to the right

(figure 6-a)

o Do not plug the unit into a UPS or

re-locatable power tap; UPS devices

should only be connected to the

SurgeX Defender Series unit

Check Front Panel

o Check the front panel to make sure the green “Outlets On” LED is lit

If the green “Outlets On” LED is lit, your Defender Series unit

is ready to be used, and is protecting your server and ancillary

equipment (figure 7-a)

o If the green “Outlets On” LED is not lit, but the red Wiring Fault Indicator

LED is lit, a wiring fault at the outlet has been detected. The SurgeX

unit will not operate until the Wiring Fault is resolved by a qualified

electrician. Refer to the “Front Panel LED Indicators” section for further

instructions (figure 7-b)

CAUTION – Do not install this device if there is not at least 10 meters

(30 feet) or more of wire between the electrical outlet and the electrical

service panel.

IV.

Common Configurations

• To properly protect your system, connect all ancillary server equipment (including UPS/Battery Backup)

to the SurgeX Defender Series output power receptacles (figure 8-a)

7-a

7-b

6-a

8-a