8 error codes – SurgeX XR315 User Manual

Page 24

Advertising
background image

24

The unit starts to power up but then immediately powers down

There are two likely causes for this: One cause is a Down input that is on all the time and over-
riding the power up function. Check the down input with a meter. The other cause is that the
Over-Ride Func menu item has been set to Master when the unit is not actually connected to
another XR315 and is in cascade mode. Change this menu item to Disable.

The unit will not go into programming mode

You must power down the unit first before you can get into the programming mode.

8

Error Codes

Error codes are displayed on the second line of the display.

Error 05

The calibration of the AC voltmeter is no longer accurate. The unit is otherwise
fully operational. Call the factory for assistance.


Error 15

There is a checksum error in the non-volatile memory. This indicates that the set-
up information could be incorrect. It is recommended that you completely check
the programming and save the settings again. If error 15 is still displayed there is
most likely a permanent problem with the non-volatile memory.


Error 16

There is an internal error. The unit will need to be returned to the factory for
repair.


Error 24

Please call the factory.