9 specifications, Specifications – SurgeX XR315 User Manual

Page 25

Advertising
background image

25

9

Specifications

Operational Voltage Range:

90 to 150 Volts AC

Current rating:

15 Amps

Power Rating:

1,800 Watts

Maximum Load Inrush Energy:

1400 Joules total during power-up

Surge Let-through Voltage:

Zero let-through Voltage for a 6000 Volt surge

Meets Federal Guidelines:

Grade A, Class 1, Mode 1 (CID A-A-55818)

EMI/RFI Filter, Normal Mode:

40 dB @ 100 KHz, 50dB @ 300 KHz, 50 dB @ 3 MHz, 50 dB @ 30
MHz (50 Ohm load)

EMI/RFI Filter, Common Mode:

18dB @ 300 KHz, 30 dB @ 1 MHz, 50 dB @ 5 MHz, 50 dB @ 20
MHz (50 Ohm load)

Maximum Applied Surge Voltage:

6,000 Volts *

Maximum Applied Surge Current:

Unlimited (due to current limiting) *

Maximum Applied Surge Energy:

Unlimited (due to current limiting) *

Endurance:

(C62.41-1991 category B3 pulses), 1 KV > 500,000;
3 KV > 10,000; 6 KV > 1000

Number of Outlets:

8

Remote Control Voltage:

5 to 30 Volts dc

Remote Control Current Draw:

4 mA maximum

Contact Closure Max. Resistance:

100 Ohms

Auxiliary Relay Contact Rating:

30 Volts dc at 1 Amp

12 Volt Output Max. Current:

40 mA

AC Voltmeter Accuracy:

± 2%

AC Ammeter Accuracy:

0.1A resolution, ±1A accuracy

Coax Protection:

Compatible with Cable Television (CATV), Digital Satellite System
(DSS), Television, Video Cassette Recorder (VCR), Cable Modem,
and TV Antenna Equipment. Approvals: UL 497B, UL Recognized.

Dimensions (no rack ears or feet): 17.3” W x 10.5” D x 1.7” H

Weight: 12 lbs (5.4kg)

Temperature Range: 5C to 35C

Humidity Range: 5% to 95% R.H. Non-condensing

Agency Listings: ETL and cETL (UL 1449, Third Edition, Type 3 Surge Protective Device; UL 1283;
CSA C22.2 No.8-M1986, R2004)


* 1.2 x 50 microsecond industry standard combination wave surge as per IEEE C62.41

0208A