Water quality, System cleaning and flushing, Cleaning and flushing – WaterFurnace Envision2 User Manual

Page 13

Advertising
background image

13

ENVISION

2

COMPACT - 50 HZ INSTALLATION MANUAL

In ground water situations where scaling could be heavy

or where biological growth such as iron bacteria will be

present, a closed loop system is recommended. The heat

exchanger coils in ground water systems may, over a period

of time, lose heat exchange capabilities due to a buildup

of mineral deposits inside. These can be cleaned, but only

by a qualified service mechanic, as special solutions and

pumping equipment are required. Hot water generator coils

can likewise become scaled and possibly plugged. In areas

Water Quality

Material

Copper

90/10 Cupronickel

316 Stainless Steel

pH

Acidity/Alkalinity

7 - 9

7 - 9

7 - 9

Scaling

Calcium and

Magnesium Carbonate

(Total Hardness)

less than 350 ppm

(Total Hardness)

less than 350 ppm

(Total Hardness)

less than 350 ppm

Corrosion

Hydrogen Sulfide

Less than 0.5 ppm (rotten egg

smell appears at 0.5 ppm)

10 - 50 ppm

Less than 1 ppm

Sulfates

Less than 125 ppm

Less than 125 ppm

Less than 200 ppm

Chlorine

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Chlorides

Less than 20 ppm

Less than 125 ppm

Less than 300 ppm

Carbon Dioxide

Less than 50 ppm

10 - 50 ppm

10 - 50 ppm

Ammonia

Less than 2 ppm

Less than 2 ppm

Less than 20 ppm

Ammonia Chloride

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Ammonia Nitrate

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Ammonia Hydroxide

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Ammonia Sulfate

Less than 0.5 ppm

Less than 0.5 ppm

Less than 0.5 ppm

Total Dissolved Solids (TDS)

Less than 1000 ppm

1000 - 1500 ppm

1000 - 1500 ppm

LSI Index

+0.5 to -0.5

+0.5 to -0.5

+0.5 to -0.5

Iron Fouling

(Biological Growth)

Iron, FE

2

+ (Ferrous)

Bacterial Iron Potential

< 0.2 ppm

< 0.2 ppm

< 0.2 ppm

Iron Oxide

Less than 1 ppm, above this

level deposition will occur

Less than 1 ppm, above this

level deposition will occur

Less than 1 ppm, above this

level deposition will occur

Erosion

Suspended Solids

Less than 10 ppm and filtered

for max. of 600 micron size

Less than 10 ppm and filtered

for max. of 600 micron size

Less than 10 ppm and filtered

for max. of 600 micron size

Threshold Velocity

(Fresh Water)

< 1.8 m/sec

< 1.8 m/sec

< 1.8 m/sec

NOTES: Grains = ppm divided by 17

mg/L is equivalent to ppm

2/22/12

with extremely hard water, the owner should be informed

that the heat exchanger may require occasional flushing.

Failure to adhere to the guidelines in the water quality table

could result in loss of warranty.

Units with cupronickel heat exchangers are recommended

for open loop applications due to the increased resistance

to build-up and corrosion, along with reduced wear caused

by acid cleaning.

System Cleaning and Flushing

Cleaning and Flushing

Prior to start up of any heat pump, the water circulating

system must be cleaned and flushed of all dirt and debris.

If the system is equipped with water shutoff valves, the

supply and return runouts must be connected together

at each unit location (This will prevent the introduction of

dirt into the unit, see Flushing with Water Shutoff Valve

Equipped Systems illustration). The system should be filled

at the water make-up connection with all air vents open.

After filling, vents should be closed.

The contractor should start the main circulator with the

pressure reducing valve makeup open. Vents should be

checked in sequence to bleed off any trapped air and to

verify circulation through all components of the system.

As water circulates through the system, the contractor

should check and repair any leaks found in the piping

system. Drain(s) at the lowest point(s) in the system should

Return Runout

Supply Runout

Mains

Rubber Hose

Runouts Initially
Connected Together

Flushing with Water Shutoff Valve Equipped Systems

Advertising