Blower performance data cont, Variable speed ecm motor, Setting blower speed - variable speed ecm – WaterFurnace Envision2 User Manual

Page 20

Advertising
background image

20

ENVISION

2

COMPACT - 50 HZ INSTALLATION MANUAL

Variable Speed ECM Motor

Model

Max

ESP (Pa)

Blower

Size

Motor

kW

Airflow DIP Switch Settings

1

2

3

4

5

6

7

8

9

10

11

12

005

124.50

229 x 178

0.37

142

189

236

283

330

378

L

M

H

006

124.50

229 x 178

0.37

189

236

283

330

378

425

472

519

566

L

M

H

009

124.50

279 x 254

0.37

307

354

401

472

519

566

614

661

708

L

M

H

012

124.50

279 x 254

0.37

307

378

425

496

543

590

637

684

732

L

M

H

015

186.75

279 x 254

0.75

378

448

519

614

708

826

920

991

1085

L

M

H

017

187.75

279 x 254

0.75

378

448

519

614

708

826

920

991

1085

L

M

H

Factory settings are at recommended L-M-H DIP switch locations
M-H settings MUST be located within boldface L/s range
Lowest and Highest DIP switch settings are assumed to be L and H respectively
Air flow is controlled within ±5% up to the maximum ESP
Max ESP includes allowance for wet coil and 25.4 mm MERV 4

6/15/12

The ABC board’s Yellow Config LED will flash the current

variable speed ECM blower speed selections for low, med,

and high continuously with a short pause in between. The

speeds can also be confirmed with the AID Tool under the

Setup/ECM Setup screen. The variable speed ECM blower

motor speeds can be field adjusted with or without using

an AID Tool.

Variable Speed ECM Setup without an AID Tool

The blower speeds for Low (G only), Med (Y1), and High

(Y2/Aux) can be adjusted directly at the Aurora ABC

board which utilizes the push button (SW1) on the ABC

board. This procedure is outlined in the variable speed ECM

Configuration Mode portion of the Aurora ‘Base’ Control

System section.

Variable Speed ECM Setup with an AID Tool

A much easier method utilizes the AID Tool to change

the airflow using the procedure below. First navigate to

the Setup screen and then select ECM Setup. This screen

displays the current variable speed ECM settings. It allows

the technician to enter the setup screens to change the

variable speed ECM settings. Change the highlighted item

using the

◄ and ► buttons and then press the ◙ button to

select the item.

Setting Blower Speed - Variable Speed ECM

Variable Speed ECM Speed Setup - These screens allow

the technician to select the low, medium, and high blower

speed for the variable speed ECM blower motor. Change

the highlighted item using the

▲ and ▼ buttons. Press the

◙ button to select the speed.

After the high speed setting is selected the AID Tool will

automatically transfer back to the ECM Setup screen.

Variable Speed ECM Setup with an AID Tool cont.

Selecting YES will enter variable

speed ECM speed setup, while

selecting NO will return to the

previous screen.

ECM SPEED INFO

LOW SPEED: 3
MED SPEED: 5
HIGH SPEED: 7

WANT TO CHANGE?

YES

OPTION ◄►

NO

ENTER ◙

ECM SPEED INFO

1
2 <– LOW
3
4
5
6
7
8
9
10
11
12

OPTION ◄►

ENTER ◙

ECM SPEED INFO

1
2 LOW
3
4
5 <– MED
6
7
8
9
10
11
12

OPTION ◄►

ENTER ◙

ECM SPEED INFO

1
2 LOW
3
4
5 MED
6
7
8
9
10
11
12 <– HIGH

OPTION ◄►

ENTER ◙

Blower Performance Data cont.