7wiring, 3 wiring examples – Pilz PDP67 F 8DI ION HP User Manual

Page 29

Advertising
background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

7-9

7.3

Wiring examples

7

Wiring

7.3.4

Example: Dual-channel, failsafe input device, with test pulse

Example: Dual-channel, failsafe input device, with test pulse

7-

Bsp 4: zweikan fehlersich Sensor getaktet

Features:

Depending on the application area and its respective regulations, this

connection diagram is suitable in accordance with EN ISO 13849-1

up to PL e and EN IEC 62061 up to SIL CL 3.

The input device must be approved for failsafe applications.

This type of connection is mainly used for signal inputs with infrequent

operation.

As the test pulses are permanently assigned to the inputs, all short

circuits will be detected, with the exception of short circuits that short

out the input device (cable from the test pulse to the input device and

cable from the input device to the input).

Bsp 4: zweikan fehlersich Sensor getaktet_Zeichnung HP

24 V

L+

L-

Dual-channel input device

with diverse channels

Please ensure safety regulations and EMC guidelines are met!

Test pulse T1

Test pulse T0

Test pulse T1

Test pulse T0

Dual-channel input device

with identical channels

Advertising