Connections, Installation – ABUS Technologies HART? Block Temperature Transmitter User Manual

Page 6

Advertising
background image

ABUS TECHNOLOGIES INC.

6


HART

Block

4. CONNECTIONS


5. INSTALLATION



Input Signal

INPUT SIGNAL

TYPE

MEASUREMENT RANGES

MINIMUM

MEASUREMENT

RANGES

Resistance

Thermometer

(RTD)

Pt100
Pt500

Pt1000

-200°C ~ 850°C (-328°F ~ 1562°F)

-200°C ~ 250°C (-328°F ~ 482°F)
-200°C ~ 250°C (-328°F ~ 482°F)

10 K
10 K
10 K

Cu50

Cu100

-50°C ~ 150°C (-58°F ~ 302°F)
-50°C ~ 150°C (-58°F ~ 302°F)

10 K
10 K

*Ni100
*Ni500

*Ni1000

-60°C ~ 180°C (-76°F ~ 356°F)
-60°C ~ 180°C (-76°F ~ 356°F)
-60°C ~ 150°C (-76°F ~ 302°F)

10 K
10 K
10 K

Resistance

Transmitter

Resistance

(Ω)

0 ~ 400 Ω

0 ~ 2000 Ω

0 ~ 10000 Ω

10 Ω
20 Ω

100 Ω

*α = 5000 ppm/K or 6180 ppm/K
Connection type: 2-,3- or 4-wire connection
Sensor current: 0.5 mA

Advertising