Lm50-tcp – CIRCUTOR LM50-TCP+ User Manual

Page 2

Advertising
background image

LM50-TCP+

M98231601-03-11A.doc1A

3.- MBUS testing software

The LM50-TCP+ device is supplied with MSDOS
software which has the main purpose of testing the
communications with the device. The software, just
like the device setup, can work with different
networking protocols and to a specific port. Its name
is MBUS.
To use the program, save the mbus.exe file to a
folder that can be accessed from MSDOS and use
this application paying attention to the networking
protocol requirements set up in the device.

3.1.- Warnings

To start communication with the LM50-TCP+ device,
ensure that the equipment is powered on and
connected to the Local Area Network (LAN) from
which the sending of the Modbus frames will be
made. Similarly, check that your computer or
Ethernet network does not have a firewall or a
security system that could prevent the said network
protocols and the ports set up in the device from
working.

Below, examples are shown in italics of the sending
of Modbus commands using the different network
protocols (UDP/TCP/ModbusTCP).

3.2.- UDP Communications (u)

With the LM50-TCP+ device set up for the UDP
protocol and a specific port (in the example 10001), an
example of sending the Modbus command is shown
below.

Example of the reading command relating to the value of the
record corresponding to digital input 2 (0082Hex).

c:\>mbus u172.16.4.130 p10001 010400820002

010400820002

CRC

01040400000000

CRC

100.00%

where:

172.16.4.130 LM50-TCP+ IP address

10001

LM50-TCP+ UDP port

100%

Response OK

3.3.- TCP communication (t)

With the LM50-TCP+ device has been set up for the
TCP protocol and a specific port (in the example
10001
), an example of sending the Modbus command
is shown below.

Example of the reading command relating to the value of the
record corresponding to digital input 2 (0082Hex).

c:\>mbus t172.16.4.130 p10001 010400820002

010400820002

CRC

01040400000000

CRC

100.00%

where:

172.16.4.130 LM50-TCP+ IP address

10001

LM50-TCP+ TCP port

100%

Response OK

3.4.- Modbus/TCP communication (x)

With the LM50-TCP+ device set up for the
Modbus/TCP protocol and port 502, an example of
sending the Modbus command is shown below.

Example of the reading command relating to the value of the
record corresponding to digital input 2 (0082Hex).

c:\>mbus x172.16.4.130 p502 010400820002

1F1000000006010400820002

CRC

1F100000000701040400000000 CRC 100.00%

where:

172.16.4.130 LM50-TCP+ IP address

502

Modbus/TCP port

100%

Response OK

3.5.- Power Studio Scada software

CIRCUTOR provides the PowerStudio software,
from which all the data coming from the LM50-TCP+
device can be viewed in real-time. Download it from

www.circutor.com

.

4.- TECHNICAL SPECIFICATIONS

Inputs features:

- Type:
- Maximum activation current:
- Minimum Ton / Toff:


Free of opto-insulated voltage (dry contact)
50 mA
50 ms / 50 ms

Power circuit:

- Single-phase (phase – neutral) A1 – A2 :
- Frequency:
- Maximum consumption:
- Working temperature:
- Water content (non-condensing):


85…265 VAC / 120…374 VDC

47…63 Hz
5 …8 V—A
-10 …..+ 60 ºC
5 ….. 95%

Mechanical features:

- Case material:
- Degree of protection of the equipment:
- Dimensions (mm):
- Weight:
- Maximum operating height:


UL94 - V0 self-extinguishing plastic
IP 20
158.2 x 57.75 x 90 mm (8 modules)
320 grams
2,000 metres

LED symbols:

- Power
- RX in blinking
- TX in blinking
- FULL/HALF (Ethernet)
- ACTIVITY
- 10M/100M
- LINK


Equipment power supply and CPU activity
Activity in the receipt of RS485 frames
Activity in the emission of RS485 frames
Green: Full Duplex connection / Yellow: Half Duplex
Activity in the Ethernet port
Green: Speed 100 Mbps / Yellow: 10 Mbps
A physical connection has been made with the Ethernet
network

Network interface:

- Type:
- Connector:
- Network protocols:


Ethernet 10BaseT / 100BaseTX self-detectable
RJ45
TCP / UDP / MODBUS TCP / HTTP

Serial interface:

- Type:
- Transmission speed (configurable):
- Data bits:
- Parity:
- Stop bit


RS485 three wires (A/B/S)
4800, 9600, 19,200, 34,800, 57,600, 115,200 bps
8
No parity, odd, even
1 / 2

Safety:

Installation category Class III / EN61010 Protection against electric shock with class II
double insulation. The equipment must be connected to a power supply circuit protected with
type gl fuses as per IEC 269 or type M, with values comprised between 0.5 and 1A. It must
be fitted with a circuit breaker switch or an equivalent device, in order to be able to
disconnect the equipment from the power supply grid. The minimum section of the power
supply cable shall be of 1mm

2

.

Standards:
IEC 60664, VDE 0110, UL 94, EN61010-1, EN55011, EN 61000-4-2, EN 61000-4-3,
61000-4-11, EN 61000-6-4, EN 61000-6-2, EN 61000-6-1, EN 61000-6-3, EN 61000-4-5
EC

5.- CONNECTIONS

DETAIL OF POWER SUPPLY AND RS485 CONNECTIONS (SLAVE DEVICES)

DETAIL OF DIGITAL INPUT 1 ACTIVATION

6.- TECHNICAL SERVICE

If you have any doubts about the operation of the unit or any malfunction, contact our service staff at CIRCUTOR, SA

CIRCUTOR, SA - Technical Assistence

Vial Sant Jordi, s/n

08232 – Viladecavalls (Barcelona), SPAIN

Tel: (+34) 93 745 29 00
email: