Single channel switching – CP Electronics VITM6-EBDSPIR-AD User Manual

Page 6

Advertising
background image

6

Single channel switching

Functions: Switches channel 1 only with occupancy, optional override switch. No dimming output.

Configured to presence detection: Turns on automatically with occupancy. Press and release down switch to turn off.
Press and release up switch to turn back on. Turns off after occupancy.

Configured to absence detection: Press and release up switch to turn on. Press and release down switch to turn off.
Turns off after occupancy.

Channel mode: Set to “Switch only”

Switch mode: Set to “2 position switch together”. Note: a single position switch can be used instead to toggle the
output, set to “1 position switch separate”.

L/OUT

L

N

SW1/UP

+

-

SW2

DOWN

DIMMING

BALLAST

DIMMING LUMINAIRE

(1-10V)

CIRCUIT PROTECTION

(IF REQUIRED)

LIVE

NEUTRAL

CENTRE BIASED

RETRACTIVE SWITCH

(240V SWITCHING)

Optional for presence,

mandatory for absence detection

L/OUT

L

N

SW1/UP

SW2

DOWN

CIRCUIT PROTECTION

(IF REQUIRED)

LIVE

NEUTRAL

CENTRE BIASED

RETRACTIVE SWITCH

(240V SWITCHING)

Optional for presence,

mandatory for absence detection

LUMINAIRE

(NON-DIMMING)

+

-

Advertising