Single channel switching – CP Electronics VITM6-EBDSPIR-AD User Manual
Page 6
6
Single channel switching
Functions: Switches channel 1 only with occupancy, optional override switch. No dimming output.
Configured to presence detection: Turns on automatically with occupancy. Press and release down switch to turn off.
Press and release up switch to turn back on. Turns off after occupancy.
Configured to absence detection: Press and release up switch to turn on. Press and release down switch to turn off.
Turns off after occupancy.
Channel mode: Set to “Switch only”
Switch mode: Set to “2 position switch together”. Note: a single position switch can be used instead to toggle the
output, set to “1 position switch separate”.
L/OUT
L
N
SW1/UP
+
-
SW2
DOWN
DIMMING
BALLAST
DIMMING LUMINAIRE
(1-10V)
CIRCUIT PROTECTION
(IF REQUIRED)
LIVE
NEUTRAL
CENTRE BIASED
RETRACTIVE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
L/OUT
L
N
SW1/UP
SW2
DOWN
CIRCUIT PROTECTION
(IF REQUIRED)
LIVE
NEUTRAL
CENTRE BIASED
RETRACTIVE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
LUMINAIRE
(NON-DIMMING)
+
-