Advanced programming – CP Electronics MWS3A-PRM-LV User Manual

Page 7

Advertising
background image

7

Advanced programming

Parameter Name

Default Value Range / Options Description

UHS5 UNLCDHS

Detector Parameters

Walk Test LED

Off

On or Off

When set to On this causes a red LED to flash on the sensor when it detects

movement. Use this feature to check for adequate sensitivity levels.

 

Time Out
(Time adjustment)

20 minutes

0-99 minutes

Once the detector is turned on, this value sets how long the lights will stay on once

movement has ceased. Select 0 for 10 second delay – use for commissioning only.

 

Manual Time Out

10 minutes

0-99 minutes

When a manual operation occurs, either via the switch input or the infrared, it

invokes the timeout period.

Example 1: a detector in presence mode has a detector timeout of 15 minutes and

a manual timeout of 3 minutes. When the user leaves the room they press the off

button. The sensor will revert to automatic after 3 minutes, and then walking back

in the room will turn the lights on.

Example 2: using the settings above, the user turns the lights off (say for a

presentation) but stays in the room. Every time a movement is detected, the

manual timeout period is re-triggered, but when it doesn’t pick up for the short

timeout period, the sensor will timeout and revert to automatic. This means the

lights may turn on inadvertently during the presentation, if the occupants are still

for the manual timeout period, so adjust the timing carefully.

 

Sensitivity On

9

1 (min) to 9 (max)

Sensitivity level for detecting movement when the detector is already on. *UHS5

sets Sensitivity On and Off to the same value.

* 

Sensitivity Off

9

1 (min) to 9 (max)

Sensitivity level for detecting movement when the detector is off. *UHS5 sets

Sensitivity On and Off to the same value.

* 

Lux time

0

0 (disabled)
1-99 minutes

If the detector measures the lux level and decides that the output needs switching
on or off as a consequence, the lux time must elapse first. If at any time during the
timed delay the lux change reverses then the process is cancelled. Lux Time
enables absence detection to be implemented with a lux off level set. When the
button is pressed, the lights will go on, regardless of ambient light level. However,

if there is sufficient ambient light, they will turn off again after the Lux Time. Note
that whenever the an external switch is pressed, whether in absence or presence
mode, if the lights were out because of the lux level, they will be immediately
turned on again for at least the Lux Time.

 

Power Up State

On

On or Off

Select No for a 30 second delay on start up. If Yes is selected, there will be no

delay on start up and the detector will always power up detecting.

 

Inhibit

4 seconds

1 to 999 seconds

When the detector turns off, a delay is instigated to prevent retriggering. In certain

circumstances this delay may not be enough. This parameter allows the delay to

be changed.

 

Factory default

-

-

Restores factory default settings

 

User Modes

Override On

-

-

If the lights are off, sending the IR command will turn them on immediately and

revert to automatic operation using the manual timeout period .

 

Override Off

-

-

If the lights are on, sending the IR command will turn them off immediately. After

the manual timeout period (described above), the sensor will revert to automatic.

 

Cancel

-

-

Cancels the on or off override, returning the detector to normal operation.

 

Switching functions

Detection Mode

Presence

Presence or
Absence

Presence mode allows the output to turn on when movement is detected and off
when movement ceases. Absence mode allows the output to turn off when
movement ceases, but must be manually turned on first.

Lux on level
(Switch level on)

9

1 to 9
For a higher
resolution a scale
of 101-199 is
available

Sets a minimum light level below which the Microwave sensor is enabled, allowing
lights to be turned on by movement.
Note: the Lux Level Off value must always be greater than the Lux Level On value.

 

Lux off level
(Switch level off)

9

1 to 9
For a higher
resolution a scale
of 101-199 is
available

Sets a maximum light level above which the Microwave sensor is disabled,
preventing lights from being turned on by movement.

 

Switch Input Modes

1 position switch
together

Default

-

Short press on, long press off.

 

2 position switch
together

-

-

Short press on, short press off.

 