Crompton Controls 3DS1- -I User Manual

Page 2

Advertising
background image

Unscrew the Contactor male terminal screws until the

clamps are fully open.

Attach the start push button contact block to the
overload as shown in the sketch below.

When correctly located only a very light force is
required to clip the block into position.

Align the overload pins according to the contactor

selection. Fit the overload pins into the contactor

terminals and tighten the terminal screws, ensuring
that all three pins are underneath the terminal clamps.

Most parts of the starters are not regarded as

serviceable items and therefore, in general, complete
components are required. The following list gives a guide
to the parts which are available and the information
required when ordering replacement parts.

In order to ensure that the correct parts are supplied
please quote the details given on the starter rating plate
and the details given on the component rating plate along
with the information shown alongside the description.

.

.

.

.

.

SPARES

Contactors – Voltage and frequency.

Contactor coils – Voltage and frequency.

Overload Units – Current range.

Mechanical interlocks.

Timers – Voltage, Frequency and Timing Range.

Isolators.

f

e

d

c

b

a

1

2

3

Use narrow bladed screwdriver to
move clip in direction of arrow 'A' as
shown on drawing right, whilst lifting
the unit from the mounting rail . This can
be done with the overload unit fitted to
the contactor if in doubt remove
o v e r l o a d u n i t f r o m c o n t a c t o r, t o
improve access to the clip.

REMOVAL OF CONTACTORS FROM

DIN FORM MOUNTING RAIL

The start contact is clipped into position adjacent to terminal
96 on the overload relay.

ASSEMBLY:

REMOVAL:

Locate contact on lower right hand
corner of overload relay moulding
and rotate anti - clockwise until
firmly clipped into place

Place small screwdrier blade
under leading edge of clip and
lever off

ASSEMBLY/REMOVAL OF START CONTACT

3

3

TECHNICAL DETAILS - OVERLOAD RELAYS

TECHNICAL INFORMATION

TECHNICAL INFORMATION

FUSE RATING FOR TYPE-2 CO-ORDINATION

O/L TYPE

RANGE

MAX FUSE

(FAST)

MAX FUSE

(SLOW)

CR09/0.25

0.16 – 0.25A

1

0.5

CR09/0.4

0.25 - 0.4A

2

1

CR09/0.63

0.4 – 0.63A

2

1

CR09/1

0.63 – 1A

4

2

CR09/1.6

1 – 1.6A

4

2

CR09/2.5

1.6 – 2.5A

6

4

CR09/4

2.5 – 4A

10

6

CR09/6

4 – 6A

16

8

CR09/8

5.5 – 8A

20

12

CR09/10

7 – 10A

20

12

CR12/13

10 – 13A

25

16

CR16/18

13 – 18A

32

20

CR25/25

18 – 25A

50

25

CR32/32

23 - 32A

63

40

CR32/40

28 - 40A

63

40

CR63/50

38 – 50A

100

63

CR63/57

48 – 57A

100

63

CR63/66

57 – 66A

100

63

OVERLOAD RELAY SETTING:

Star Delta Starters are normally supplied with Thermal
Overload Relays indicating the Direct On Line
Current settings. During commissioning the Motor Full Load
Current must be set according the equivalent Star
Delta Range in the chart below;

Note: Star Delta Phase Current equals Direct On Line
Current multiplied by 1.732.

Crompton Components Ltd
Monckton Road,
Wakefield,
West Yorkshire WF2 7AL
Tel: (01924)368251
Fax: (01924)367274
E-mail: [email protected]

OVERLOAD CHARACTERISTICS

All information contained in this publication is, as far as
possible, correct at the time of going to print. however, due
to our policy of continued improvement, we reserve the
right to alter specifications without prior notice.

All goods are guaranteed for two years from date of
purchase. This does not affect the statutory rights of
user.

TECHNICAL DETAILS –
TIMERS, THERMISTOR PROTECTION UNITS

See separate booklet Ref: - BCC 2069 (Timers)
Ref: - BCC 2072 (Thermistors)

CONTACTOR DETAILS

PARAMETER

CC09~12

CC18

CC25

CC32

CC40~65

Coil Inrush VA
Closed VA

60

7

60

7

90

7.5

90

7.5

200

20

Aux. Contact 415V
rating (AC15)A

2.5

2.5

2.5

2.5

2.5

Max. Cable size:
Main Terminals
mm²

2x4

2x6

2x6

2x10

2x16

Aux. Terminals mm²

2x2.5

2x2.5

2x2.5

2x2.5

2x2.5

TECHNICAL DETAILS - CONTACTORS

CR09 TO CR80 TRIPPING CURVE

WARRANTY

Bk008 Issue 1

(10/10)

RATINGS (AC3)-AMPS

DIRECT ON LINE- TYPE 3DL

STARTER MAXIMUM

STARTER REF

3 PHASE

220V

415V

3DL1***

12

12

3DL2***

18

18

3DL3***

25

25

3DL4***

32

32

3DLA5***

40

40

3DL5***

60

60

3DL6***

65

65

1 PHASE

240V

480V

12

9

18

14

25

19

32

24

40

30

60

45

65

49

RATINGS (AC3)-AMPS

STAR-DELTA TYPE 3SD

STARTER MAXIMUM

STARTER REF

3 PHASE

220V

415V

3SD1***

21

21

3SD2***

31

31

3SD3***

43

43

3SD4***

55

55

3SD05***

85

85

3SD06***

98

98

3SDA5***

69

69

PARAMETER

Aux. Contact rating
415V(AC15)

Ambient
Temperature
Compensation

Max. Cable size:

2

Main Terminals mm

2

Aux. Terminals mm

2.5

-40°C to +60°C

2x4

2x6

2x16

2x2.5

2x2.5

2x2.5

2.5

2.5

CR09-25

CR32

CR40-63