Installation instructions

General Information

Read these instructions carefully right up to the
end before starting to mount the device! The in-
stallation has to be done by qualified profession-
al personnel. The current laws and regulations
so as the generally accepted engineering prin-
ciples have to be observed during mounting and
fitting, especially EN1434 part 1+6, (in Germany
also AGFW directive FW202, FW510, FW218
and DIN4713 part 4 and the initial verification di-
rective). At devices with M-Bus the general rules
of technology and the respective regulations for
electrical installations have to be followed.Make
sure no heating water escapes during installation

this can cause burns!

The maximum heating water temperature at the
flow sensor may not exceed depending on ver-
sion 90°C respectively 130°C. For heating water
temperature over 90°C or using as a cooling me-
ter, the detachable calculator has to be mounted
separately with the supplied mounting adapter.

For heating systems with a lack of temperature
mixing resp. with temperature stratification a
straight pipeline of min. 10xDN has to be pro-
vided upstream of the installation point.
The flow measuring section is wear-free because

no moving parts. No inlet or outlet sections are
necessary. It is important to ensure adequate
system pressure to avoid cavitation. The review
of the approval can be identified definitely in the
display menu (Level 3).
ZENNER recommends to use direct temperature
measurement and not to use immersion sleeves.

Mounting flow sensor (VMT)

Mount ball valves up- and downstream of the
VMT.

Consider the correct installation point (supply
or return). Normally this ist the return pipe
(cooler pipe at heating systems). Please note
the type plate information.

Consider the correct flow direction. This is
indicated by an arrow on the side of the VMT.

The flow sensor can be installed in any posi-
tion (also „overhead“).

Do not install at highest point of piping to
avoid air inside the flow sensor.

Consider the dimensions of the heat meter.